background image

 

21

4.2 Pressure Testing 

4.2.1 Pressurise and inspect system 

On completion of system filling, close the valve at bleed point 

B

.  This will cause the system 

pressure to rise as the filling station pump will now be dead-heading.  Using the regulator on 
the filling station (if fitted) set the outlet pressure to 5.5 bar (or as high as possible if 5.5 bar 
cannot be achieved). 

Close  the  filling  point  ball  valve  and  stop  the  filling  station  pump.    Disconnect  the  filling 
station hoses from filling point 

A

 and bleed point 

B

.  Check that neither valve is leaking fluid 

Over  a  period  of 

at  least  45  minutes

,  inspect  the  complete  installation  for  evidence  of 

leakage from any joints or pipework and repair as necessary.  Monitor the system pressure – 
if a pressure drop is seen, this indicates a leak.  All leaks 

must 

be located and rectified as a 

loss  of  system  pressure  may  lead  to  freezing  during  the  winter  months,  causing  severe 
damage to the system. 

4.2.2 Set system pressure 

Using  the  pressure  relief  valve  (so  as  to  confirm  its  correct  operation)  reduce  the  system 
pressure to 3.5 bar by turning the head of the valve by hand.  Ensure the valve closes when 
released and that the flow of fluid ceases. 

 

4.3 Sensor Installation 

Referring to the Solar System Controller instruction booklet, install and secure the sensors in 
the cylinder sensor pockets and wire the control unit.  The panel sensor should already have 
been fitted in Step 3.2.4. 

  Ensure sensor 

T1

 (with the 

black cable

) is fitted in the 

sensor pocket at the panel

 and 

that it is wired to the 

T1 terminals

 of the control unit. 

  Ensure  sensor 

T2

  (with  a 

grey  cable

)  is  fitted  in  the 

lower  sensor  pocket  of  the 

cylinder

 and that it is wired to the 

T2 terminals

 of the control unit. 

  Ensure  sensor 

T3

  (also with  a 

grey  cable

)  is fitted  in  the 

upper  sensor  pocket  of  the 

cylinder

 panel and that it is wired to the 

T3 terminals

 of the control unit. 

 

Figure 21: Sensor installation 

If the sensors are not correctly located and wired, the system will not perform correctly and 
may not operate at all. 

If  there  is  only  1  sensor  pocket  on  the  cylinder,  install  the  T2  sensor  in  the  pocket  and  do 
NOT use the T3 sensor i.e. leave the T3 terminals of the control unit unwired. 

T1 – Black Cable 

to collector sensor pocket 

B

ro

w

n

B

lu

e

SSC~ Control Unit

 

T1

 

T2

 

T3

 

T2 –

 Grey Cable 

to cylinder lower sensor pocket 

T3 –

 Grey Cable 

(if fitted) 

to cylinder upper sensor pocket 

Summary of Contents for Solar SHP20

Page 1: ...structions Maintenance Instructions Guarantee Registration Solar Thermal Systems European Solar Keymark Approved Products covered by this manual Solar SHP20 SHP30 Heat pipe vacuum tube collectors and...

Page 2: ......

Page 3: ...Connect pump station pipework 16 3 5 Electrical Installation 17 3 5 1 Mount controller 17 3 5 2 Connect external wiring centre 17 3 5 3 Connect back up heat source 18 4 Commissioning 19 4 1 System Fil...

Page 4: ...l standards and or the manufacturer s instructions This equipment is only suitable for use in a sealed solar thermal system filled with the system fluid supplied or specifically recommended by the man...

Page 5: ...turer s instructions The equipment can be regarded as electrically safe when connected to an effective earthing system installed in accordance with the requirements of current regulations This fundame...

Page 6: ...50 x 2100 x 154 Weight empty kg 66 5 95 0 Fluid volume litres 1 2 1 7 Operating data Rated flow rate per collector litres min 2 0 3 0 Max flow rate per collector litres min 20 Max operating pressure b...

Page 7: ...se thermal losses similar to a vacuum flask Vacuum Tube High efficiency twin wall glass tube with 360 0 advanced Al N Al coated absorber surface applied by Magnetron Sutter CVD for maximum absorption...

Page 8: ...ssure Relief Valve Flow from Collector Return to Collector Flow to Solar Coil Return from Solar Coil Filling Point Circulating Pump Flow Adjuster Flow Indicator Pressure Gauge Flow Temperature Gauge R...

Page 9: ...ine Pump Station Pressure Relief Discharge Solar Expansion Vessel Motorised Valve if required Drain Cock at lowest point DHW Storage Cylinder Solar Coil Boiler Coil if applicable T3 T2 T1 T1 T2 T3 Sol...

Page 10: ...to 30m 15mm 1 x SEV18 up to 40m 22mm 1 x SEV18 up to 75m 22mm 2 x SEV18 50 up to 10m 15mm 1 x SEV18 up to 45m 22mm 2 x SEV18 Table 2 Pipework and expansion vessel sizing NOTE The total length of pipe...

Page 11: ...9 2 5 Collector Pressure Drop Figure 6 SHP20 collector pressure drop Figure 7 SHP30 collector pressure drop...

Page 12: ...east South west East West North east North west North 30 0 Recommended 4 3 loss 15 loss 27 loss 32 loss 45 0 1 8 loss 7 1 loss 20 loss 36 loss 40 loss 600 7 8 loss 14 loss 28 loss 44 loss 53 loss Dat...

Page 13: ...racket spacing is within the guidelines below As much as is possible space each set of brackets equally either side of each collector centreline In some instances depending on the tile design it may b...

Page 14: ...lied with the manifold to the lower end of the support frame and secure in place by tightening the clamps Ensure the clamps either side of the bottom rail face inwards towards it and that the edges of...

Page 15: ...on kit Solar SHPX Provide effective lightening protection by connecting a suitable conductor to either the flow or return connection of EACH collector installed Connect the pre insulated flexible hose...

Page 16: ...tube manifold installations respectively 3 3 1 Install slate roof brackets Using suitable fasteners not supplied fix the brackets to the most convenient rafters ensuring the bracket spacing is within...

Page 17: ...described in Section 3 2 3 bolting the brackets to the underside of the support frame rails using the same bolts that secure the manifold and bottom rail to the rails 3 3 3 Connect manifold pipework...

Page 18: ...o A must be the flow from the collector i e the end of the collector with fitted with the temperature sensor pocket Connect the pipework running from the solar coil of the DHW storage cylinder or swim...

Page 19: ...wiring centre via a fused spur isolator 3 5 2 Connect external wiring centre Specify an appropriate 5 wire motorised valve not supplied and connect it as shown Connect the high limit thermostat of the...

Page 20: ...stat not supplied If in doubt consult the cylinder manufacturer Only if connecting to an open vented cylinder can the back up heat source be connected directly to the system controller without a motor...

Page 21: ...sary release air by depressing the valve centre pin or top up with a foot pump 4 1 2 Calculate system volume Calculate the system volume referring to the cylinder manufacturer s instructions for the v...

Page 22: ...the circulating pump by accessing the HND Menu and setting HND1 to On Ensure that any motorised valve is activated and that the pump on the pump station is turning Bleed any air from the pump using th...

Page 23: ...d of the valve by hand Ensure the valve closes when released and that the flow of fluid ceases 4 3 Sensor Installation Referring to the Solar System Controller instruction booklet install and secure t...

Page 24: ...rame and manifold correctly installed as per Section 3 2 3 insert the heat exchanger end of the tube into the manifold Support the bottom end of the tube with your hand then slide on the tube end supp...

Page 25: ...ster Turn the flow adjuster to its mid position F which gives the maximum flow rate Read the flow rate from the flow indicator The reading is taken from the bottom edge of the float body Is the readin...

Page 26: ...e pressurised and bled using Warmflow Solar Fluid SF and an appropriate filling station 5 2 2 Check fluid health CAUTION The fluid may be EXTREMELY HOT Draw off a small amount of fluid via the bleed p...

Page 27: ...s in the solar circuit at all joints and valve seals 6 Colour check of the heat transfer medium 7 Acidity check of the heat transfer medium pH only if discoloured 8 Frost protection level of the heat...

Page 28: ...tent persons in accordance with the manufacturer s instructions and all relevant regulations and codes of practice in force at the time i each service record being completed and proof of purchase and...

Page 29: ...27 7 INSTALLATION NOTES Please use this section to record any important notes relevant to the installation which may be required for future reference...

Page 30: ...0869 WARMFLOW Customer Care Centre UK 028 9262 1515 ROI 048 9262 1515 Email service warmflow co uk THIS MANUAL IS ACCURATE AT THE DATE OF PRINTING E OE BUT MAY BE SUPERSEDED AND SHOULD BE DISREGARDED...

Page 31: ...ansion vessel bladder pressure checked prior to system filling tick Bladder pressure bar 10 System flushed then filled with Warmflow Solar Fluid tick 11 System flushed of all air filling station run f...

Page 32: ...ow using one of the 3 methods below By Post Using the prepaid envelope or otherwise to Warmflow Engineering Co Ltd Appliance Registration Department Lissue Industrial Estate Moira Road Lisburn BT28 2R...

Reviews: