Instructions condensing Air heaters type HR version HR-GB-4001-a
Page
2 Then
check the CO
2
in Low fire. (mode 2)
The CO
2
in low fire is lower than the high fire
CO
2
.
Decrease the CO
2
turn the Offset adjuster to the left.
Increase the CO
2
turn the Offset adjuster to the right
After adjusting the CO
2
in Low fire, return to high fire, and Readjust the CO
2
with the Ratio
adjuster.
Then return to Low fire again and eventually readjust the CO
2
with the Offset adjuster.
Repeat these steps until both values are OK.
Never forget to check the CO (carbon monoxide ) production of the heater!!! Too much CO
means mostly that the mixture is too rich. CO value should always be below 100 ppm.
8
Problem solving
8.1 General
When it turns out that the problem is
not
caused by the external circumstances (i.e. no electric
supply power or no gas), please take the following instructions into account. Please remember
the built in waiting times of the heater (do not react too soon!) and the signals of the LEDs and
the code on the display on the electronic circuit board.
Volatile lock out
Can only be reset by hand
Display
Explanation
Cause
L-0
Internal
error
Internal error
13
L-1
Ignition
error
After ignition only 5 seconds flame
1
No flame
2
L-2
L-3
Internal
error
Internal error
13
L-4
E- error longer than 24hr
12
L-5
Burner fan
Burner fan does not work.
6
L-6
L-7
Burner fan
Burner fan rotates at the wrong speed.
7
L- 8, 9,
10, 11,
12
Internal
error
Internal error
13
L-13
Pressure
switch
Pressure switch is closed in stand by
14
L-14
Pressure
switch
Pressure switch does not close at pre-purge
11
L-15
Overheat
Sensor heat exchanger is overheated
3
L-16
Flue temp.
Flue sensor is overheated
3
L-17, 18,
19
Internal
error
Internal error
13
L-20
Flame error
Flame detected after closing gas valve
15
L-21
Flame error
Flame detected before opening gas valve
16
L-20
Flame error
Flame failure during burning detected
5
L-25
Sensor
error
Sensor heat exchanger fault
4
L-26
Sensor
error
Flue sensor fault
4
L-27, 28,
29, 30,
31
Internal
error
Internal error
13
L-32
Sensor
Sensor heat exchanger fault
4