Fixed limit value
AF7
AF8
Timer (tFCt)
The timer issues an outlet signal which is available for the binary functions. This will help you realize e.g. a
time-limited controlling or a time-dependent switching of the desired value. The timer value will not be saved
during a power outage. The time remains inactive after the return of current.
ConF
->
tFCt
->
Parameter
Value
Description
Function
FnCt
0
Timer turned off
1
Timer signal is
“high“ while timer is running
2
Timer signal is
“low“ while timer is running
Start condition
Strt
0
Manual start through function key or binary signal (no re-
start after power outage)
1
Automatic start after
‘power on‘ (restart after power out-
age); manual start also possible
Time unit
Unit
0
mm:ss
1
h:mm
2
hhh.h
Timer value
t1
00.00.
...
999.9.
Runtime of timer (in the preset time unit)
Tolerance band
toLt
0
... 9999
Tolerance band for the start of the timer. The timer will not
start before the actual value hasn’t reached the tolerance
band. 0 = start without tolerance band
1
0
X
AL
HySt
1
0
X
AL
HySt