Controller (Cntr)
The controller receives the actual value from the analog input.
ConF
->
Cntr
->
Parameter
Value
Description
Type of controller
CtyP
1
Two-point controller
2
Three-point controller
3
Steady controller
Control direction
CACt
0
Direct (the output level of the controller will be > 0, if the
actual value is large than the desired value; e.g. cooling)
1
Inverse (the output level of the controller will be > 0, if the
actual value is smaller than the desired value, e.g. heat-
ing)
Manual output level
HAnd
-100...
0 ...
+101
Output level after switching into manual operation 101 =
last output level
Output level for Out-of-Range
rOut
-100...
0
...
+100
Output level for exceeding or falling short of the measur-
ing range
Limit for desired value
– start
SPL
-1999
...
+9999
A limit for the desired value will prevent entering values
which are outside the determined range. The limits for
desired values do work if the desired value will be input
via the interface. The correction value will be limited for
an external desired value with correction.
Limit for desired value- end
SPH
-1999 ...
+9999
(Setup program: manual operation and self-optimization can be locked.)
Ramp Function / Firing Curve (rAFC)
The device can be used as a fixed value controller with or without ramp function. A firing curve is supported
additionally
.
ConF
->
rAFC
->
Parameter
Value
Description
Function
FnCt
0
Ramp function/ firing curve turned off
1
Ramp function Kelvin/ minute
2
Ramp function Kelvin/ hour
3
Ramp function Kelvin/ day
4
Firing curve Kelvin/ minute
5
Firing curve Kelvin/ hour
6
Firing curve Kelvin/ day
Ramp gradient
rASL
0
…
999
Value of ramp gradient (only for function = 1 to 6)
(Setup program: you can set the time value, time unit and desired values for the firing curve here.)