background image

 

 

 
 

16 

WDC200-NX Electronic Water Management. 

Revision-2 

 

7.2  Standard View 

 

Figure 4. Standard view 

 The standard view can rotate between the Notifications screen and IO screen using 
the 

 and 

 buttons.  

7.2.1 Notifications 

The notifications screen will show the name of the configuration at the top, and the 
currently active system notifications below. The notification name is based on the 
hierarchy of the system in the configuration structure. Where the notification contains 
a value element, the value will be shown on the right. The notifications will also show 
as different colours to differentiate the functionality. 

 

 

Summary of Contents for WDC100-NX Series

Page 1: ...Product Manual WDC200 NX Series Electronic Water Management Controller ...

Page 2: ...iance can be used by persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved If the supply cord is damaged it must be replaced by Wallgate its service agents or similarly qualified persons in order to avoid hazard AS 1172 Cert...

Page 3: ...Contents 10 5 2 Advice on attaching the unit 10 5 3 Connections 10 5 4 Connect the Electrical Supply 13 6 Piezo touch button and infrared sensor controls 14 7 Screen Navigation 14 7 1 Navigation Buttons 14 7 2 Standard View 15 7 2 1 Notifications 15 7 2 2 WDC100 NX WDC200 NX 16 7 3 Configuration Settings 17 7 4 Quick Functions 17 7 5 Device Information 18 7 6 System Functions 21 8 WDC Configuratio...

Page 4: ... 8 7 Lockout 23 8 8 Hygiene Purge 24 8 9 W C 24 8 10 Shower 24 8 11 Tap 24 9 WDC NX 100 Configuration Settings 25 10 System Test Function 36 11 Data Logging 36 12 Technical Specifications 37 13 Operation 37 14 Maintenance 38 15 Related Documentation 38 ...

Page 5: ...at any time without prior notice This manual is specific to the product that it has been supplied with at the date of supply Without prejudice to any warranties in Wallgate Limited s terms and conditions of sale any warranty will be invalidated if the equipment is installed or serviced by unqualified personnel No part of this publication and the information contained may be reproduced transmitted ...

Page 6: ...to heed these warnings can have serious consequences WARNING This is a warning 2 2 Note A note with amber text on a white background is used to draw your attention to important and useful information NOTE This is a note 2 3 Numbered procedures Steps in procedures are numbered starting from 1 1 This is step 1 2 This is step 2 etc 2 4 Bullet lists A bullet list is used to give information that is no...

Page 7: ... WDC control units to a dedicated PC or laptop computer You can manage the WDC units through the network You can also adjust time cycle settings lockout settings remote water isolation on individual units or groups RTC settings etc You can also view the unit status in real time and log data Data Logging Activations of the Inactivity Purge function detailed below are logged in memory and then using...

Page 8: ...ay clock used by the WDC200 NX for program features such as Time Slots and Inactivity Purge System Test The System Test is a feature that allows you to operate switches and piezo touch buttons and make sure that these operate the necessary outputs such as lights or valve solenoids Time Slots Usage of services such as basins showers and WC pans can be controlled using pre set time slots For example...

Page 9: ...menu system with security controlled access Independent control of multiple outlets Fully configurable precise time control of water valve operation that is fully adjustable in situ by the installer customer Lockout functions to prevent product misuse that is fully adjustable for the number of user operations operations period lockout period Single or dual flush for WC control Piezo touch button i...

Page 10: ... unit are readily visible and accessible WARNING Do not mount the unit upside down The control box has four holes for attaching the unit to the wall using four round head screws 5 3 Connections All cables must be connected to the unit using the sockets at the bottom of the unit enclosure Piezo IR input cables solenoid valve output cables and all CAN LAN connections are plug and play fittings with ...

Page 11: ... valve 5 Output to Room 2 WC Flush valve Opens Room 2 WC Flush valve 6 Output to Room 2 Shower valve Opens Room 2 Shower valve 7 Output to Room 2 Basin Bath cold valve Opens Room 2 Basin Bash cold valve 8 Output to Room 2 Basin Bath hot valve Opens Room 2 Basin Bath hot valve A Input from Room 1 WC Flush piezo touch button User input piezo button or IR sensor for Room 1 WC Flush B Input from Room ...

Page 12: ...top Room 2 Commissioning Purge M Room 1 Auxiliary 3 Input to set Room 1 Remote L O N Room 2 Auxiliary 3 Input to set Room 2 Remote L O O Room 1 Auxiliary 4 Input for Room 1 WC Remote Flush P Room 2 Auxiliary 4 Input for Room 2 WC Remote Flush CAN CAN Link Sockets CAN port connections to interface with external control devices e g WEX300 LAN Network Link Socket LAN connection to WDCMS Screened Ethe...

Page 13: ...earth conductor to the water supply pipes on the basin and shower nozzles The other end of the earth conductor must be connected to an approved earth facility NOTE The water pipes connected to the basin taps and shower nozzles must be bonded to earth 3 Make sure that the input leads from the basin tap shower and WC are plugged into the correct sockets on the base of the control unit 4 Complete ele...

Page 14: ...ls Piezo touch buttons and infrared sensors can be connected to the control unit to operate the basins showers WCs etc the unit will support piezo infrared sensor active or momentary tactile switches The WC flush valve is set to deliver a 6 litre full flush The controller will support electronic cisterns and or direct flush valves ...

Page 15: ...igate back to previous menu level or screen press and hold for quick functions Enter Enter new menu level press and hold for system menu Up Scroll up in vertical menus and to the right in horizontal menus press and hold for system status Down Scroll down in vertical menus and left in horizontal menus press and hold for configuration ...

Page 16: ...ications The notifications screen will show the name of the configuration at the top and the currently active system notifications below The notification name is based on the hierarchy of the system in the configuration structure Where the notification contains a value element the value will be shown on the right The notifications will also show as different colours to differentiate the functional...

Page 17: ...ngs Version The version number of the application IP Address The current last IP address of the unit Date Time The system date and time IOs The WDC device Inputs Outputs CAN and ethernet are depicted here Input indicators will fill as green while the corresponding input is active Outputs indicators will fill as green while the corresponding output is active CAN indicators will turn green for 100ms...

Page 18: ...current position in the menu tree can be seen at the top of the screen For a description of the menu and settings please see the Error Reference source not found section After a minute of inactivity the Configuration Settings screen will close and change to the Notifications screen If a setting editor is open when this occurs the editor will be cancelled and the setting will not saved 7 4 Quick Fu...

Page 19: ...ring number Hardware Configuration WDC100 NX WDC200 NX Time Date Current time and date of the unit Run Time The time since the last restart of the unit App Version Version number of the device application firmware App Date Date the application firmware was built Pri Boot Version Version number of the device primary bootloader firmware Pri Boot Date Date the primary bootloader firmware was built Se...

Page 20: ...ddress of the network gateway UDP Tx Counter Number of ethernet UDP packets transmitted to the server UDP Rx Counter Number of ethernet UDP packets received from the server Appeth State State of the connection to ethernet COMMS State State of the connection to the server Bluetooth MAC MAC address of the Bluetooth device Table 4 Device network information view Page Info Description Tasks List of ta...

Page 21: ... CRC CRC calculated on the configuration file data including setting changes Table 7 Device configuration information view Page Info Description Bar graph Progress of the logging system Grey is unlogged space Orange is logged but hasn t been marked as read Green is logged and marked as read Write Address Flash address where the next log will be written Next ID ID for the next new log Marked Addres...

Page 22: ...lt Config File Revert the device configuration settings to their default values Test Mode Restart the unit in test mode In test mode pressing the inputs will set their corresponding outputs Set Date Time Set the time and date of the system Factory Test Restart the unit in factory test mode This is for use during production Table 9 System functions view After a minute of inactivity the System Funct...

Page 23: ...d Factory This is used when programming the unit during factory production Normal This is for normal operation of the Bluetooth module Using BLE the WDC device will advertise itself with the string defined in Bluetooth Advertise Name or if undefined with WDC SERIAL NUMBER where SERIAL NUMBER is the serial number of the WDC device 8 2 Commissioning Purge The commissioning purge will sequentially ru...

Page 24: ... time specified in the WC Occupy Half Flush Time setting a half flush will be scheduled to run on the WC If the user remains for more than the time specified in the WC Occupy Full Flush Time setting a full flush will be scheduled to run on the W C When the user moves away from the IR sensor the system will wait for the Vacate Time to pass before activating the scheduled Half or Full flush action o...

Page 25: ...do anything to the shower cycle unless Interruptible is enabled in which case the shower cycle will be cancelled As the shower nears the end of its cycle it is possible to have the valve pulse off and on again as a warning if the Shower End Warning Pulse is enabled How long the water is pulsed off can be set with the Pulse Length and the Pulse Time from End setting can be used to specify how long ...

Page 26: ...tion Count 0 255 1 2 1 2 Time Slots 2 1 2 1 Schedules Schedule List 1 00 00 00 06 00 00 Enabled 2 06 00 00 12 00 00 Enabled 3 12 00 00 18 00 00 Enabled 4 18 00 00 00 00 00 Enabled 5 00 00 00 00 00 00 Disabled 6 00 00 00 00 00 00 Disabled 7 00 00 00 00 00 00 Disabled 8 00 00 00 00 00 00 Disabled 9 00 00 00 00 00 00 Disabled 10 00 00 00 00 00 00 Disabled 11 00 00 00 00 00 00 Disabled 12 00 00 00 00 ...

Page 27: ...cate Time Time HH mm ss ms 00 00 00 1 00 00 59 0 00 00 10 0 2 1 5 2 WC Occupy Half Flush Time Time HH mm ss ms 00 00 00 1 00 59 59 0 00 00 18 0 2 1 5 3 WC Occupy Full Flush Time Time HH mm ss ms 00 00 00 1 00 59 59 0 00 00 45 0 2 1 5 4 IR Walkaway Enable Disable Disabled 2 1 6 Lockout 2 1 6 1 Cycle Period Time HH mm ss 00 01 00 23 59 59 00 15 00 2 1 6 2 Cycle Activations 0 255 4 2 1 6 3 Lockout St...

Page 28: ... Activations Enable Disable Enabled 2 2 3 Auto Run 2 2 3 1 Event Schedules Event Schedule List 1 00 00 00 Disabled 2 00 00 00 Disabled 3 00 00 00 Disabled 4 00 00 00 Disabled 5 00 00 00 Disabled 6 00 00 00 Disabled 7 00 00 00 Disabled 8 00 00 00 Disabled 9 00 00 00 Disabled 10 00 00 00 Disabled 11 00 00 00 Disabled 12 00 00 00 Disabled 13 00 00 00 Disabled 14 00 00 00 Disabled 15 00 00 00 Disabled...

Page 29: ...kout Penalty Time HH mm ss 00 01 00 23 59 59 01 00 00 2 3 2 Time Slots 2 3 2 1 Schedules Schedule List 1 00 00 00 06 00 00 Enabled 2 06 00 00 12 00 00 Enabled 3 12 00 00 18 00 00 Enabled 4 18 00 00 00 00 00 Enabled 5 00 00 00 00 00 00 Disabled 6 00 00 00 00 00 00 Disabled 7 00 00 00 00 00 00 Disabled 8 00 00 00 00 00 00 Disabled 9 00 00 00 00 00 00 Disabled 10 00 00 00 00 00 00 Disabled 11 00 00 0...

Page 30: ...ss ms 00 00 00 0 00 00 59 0 00 00 01 0 2 3 11 Pulse Time from End Time HH mm ss ms 00 00 00 0 00 00 59 0 00 00 08 0 2 3 12 Interruptible Enable Disable Enabled 2 4 Tap 2 4 1 Lockout 2 4 1 1 Cycle Period Time HH mm ss 00 01 00 23 59 59 01 00 00 2 4 1 2 Cycle Activations 0 255 10 2 4 1 3 Lockout State Enable Disable Enabled 2 4 1 4 Lockout Penalty Time HH mm ss 00 01 00 23 59 59 01 00 00 2 4 2 Auto ...

Page 31: ... Purge 2 4 6 1 Operation Time Time HH MM ss ms 00 00 00 1 00 10 00 0 00 10 00 0 2 4 7 Cycle Time Time HH mm ss ms 00 00 00 1 00 05 59 9 00 00 10 0 2 4 8 System Normal E Suite Normal 2 4 9 Tap End Warning Pulse Enable Disable Disabled 2 4 10 Pulse Length Time HH mm ss ms 00 00 00 0 00 00 59 0 00 00 01 0 2 4 11 Pulse Time from End Time HH mm ss ms 00 00 00 0 00 00 59 0 00 00 08 0 2 4 12 Interruptibl...

Page 32: ... Time HH mm ss ms 00 00 00 1 00 00 59 0 00 00 10 0 3 1 5 2 WC Occupy Half Flush Time Time HH mm ss ms 00 00 00 1 00 59 59 0 00 00 18 0 3 1 5 3 WC Occupy Full Flush Time Time HH mm ss ms 00 00 00 1 00 59 59 0 00 00 45 0 3 1 5 4 IR Walkaway Enable Disable Disabled 3 1 6 Lockout 3 1 6 1 Cycle Period Time HH mm ss 00 01 00 23 59 59 00 15 00 3 1 6 2 Cycle Activations 0 255 4 3 1 6 3 Lockout State Enabl...

Page 33: ... Disabled 11 00 00 00 Disabled 12 00 00 00 Disabled 13 00 00 00 Disabled 14 00 00 00 Disabled 15 00 00 00 Disabled 16 00 00 00 Disabled 17 00 00 00 Disabled 18 00 00 00 Disabled 19 00 00 00 Disabled 20 00 00 00 Disabled 21 00 00 00 Disabled 22 00 00 00 Disabled 23 00 00 00 Disabled 24 00 00 00 Disabled 25 00 00 00 Disabled 26 00 00 00 Disabled 27 00 00 00 Disabled 28 00 00 00 Disabled 29 00 00 00 ...

Page 34: ...0 00 00 00 Disabled 15 00 00 00 00 00 00 Disabled 16 00 00 00 00 00 00 Disabled 3 3 2 2 Log Activations Enable Disable Enabled 3 3 3 Auto Run 3 3 3 1 Event Schedules Event Schedule List 1 00 00 00 Disabled 2 00 00 00 Disabled 3 00 00 00 Disabled 4 00 00 00 Disabled 5 00 00 00 Disabled 6 00 00 00 Disabled 7 00 00 00 Disabled 8 00 00 00 Disabled 9 00 00 00 Disabled 10 00 00 00 Disabled 11 00 00 00 D...

Page 35: ...d 2 00 00 00 Disabled 3 00 00 00 Disabled 4 00 00 00 Disabled 5 00 00 00 Disabled 6 00 00 00 Disabled 7 00 00 00 Disabled 8 00 00 00 Disabled 9 00 00 00 Disabled 10 00 00 00 Disabled 11 00 00 00 Disabled 12 00 00 00 Disabled 13 00 00 00 Disabled 14 00 00 00 Disabled 15 00 00 00 Disabled 16 00 00 00 Disabled 17 00 00 00 Disabled 18 00 00 00 Disabled 19 00 00 00 Disabled 20 00 00 00 Disabled 21 00 0...

Page 36: ...00 00 00 Disabled 3 4 5 2 Log Activations Enable Disable Enabled Menu Item Type Default 3 4 6 Hygiene Purge 3 4 6 1 Operation Time Time HH MM ss ms 00 00 00 1 00 10 00 0 00 10 00 0 3 4 7 Cycle Time Time HH mm ss ms 00 00 00 1 00 05 59 9 00 00 10 0 3 4 8 System Normal E Suite Normal 3 4 9 Tap End Warning Pulse Enable Disable Disabled 3 4 10 Pulse Length Time HH mm ss ms 00 00 00 0 00 00 59 0 00 00 ...

Page 37: ... been connected to the correct sockets on the control unit NOTE The control unit cannot set the water temperature for pre mixed supplies or showers For these applications seek advice from the plumbing contractor or architect TMV3 thermostatic valves are usually used in these applications 11 Data Logging Data logging records the events of all functionalities including the hygiene purge operations T...

Page 38: ...ve the cover of the electronic control box The basin shower and WC are fitted with either Piezo type stainless steel touch buttons or infrared sensors Press the button face to operate a Piezo touch button Once an operation cycle starts it will continue for a fixed period and stop unless the touch button is pressed again which will cancel the operation The controller has extensive menu settings all...

Page 39: ...to suit the system flow performance A dual flush option is available using one or two buttons depending on the configuration of the WDC NX controller 14 Maintenance We offer a comprehensive service package details of which can be obtained from our customer service department A spare parts service is also available The electronic control unit does not have any user serviceable parts In the event of...

Page 40: ...Wallgate Ltd Crow Lane Wilton Salisbury Wiltshire SP2 0HB England tel 44 0 1722 744594 fax 44 0 1722 742096 email service wallgate com web www wallgate com ...

Reviews: