2
WT.025.055.004.UA.IM.0814
MANUAL CHLORINATOR - 3000LB/24HR
EVOQUA
W3T109620
1.1
Technical Data
Accuracy
4% of indicated flow
Capacity
50 to 3000 lb/24 hr chlorine
Feed Range
20 to 1 for any one rotameter
Pressure at Point of
Application
75 psi max. with flexible polyethylene for
the solution line.
160 psi max. with high pressure hose or rigid
pipe for the solution line.
Minimum Injector Inlet
Pressure
20 psi is required by the two-inch pressure
operated plug shut-off injector; also the 3/4-
inch and one-inch fixed throat anti-syphon
injectors.
Maximum Injector Inlet
Pressure
See Dwg. 25.055.190.010