background image

36

Venting

INSTALLATION INSTRUCTIONS

Venting for Direct-Vent Water Heater (cont.)

In the Commonwealth of 

Massachusetts

The Commonwealth of Massachusetts requires 

compliance with regulation 248 CMR 4.00 and 5.00 for 

installation of through-the-wall vented gas appliances as 

follows:
5.08: Modifications to NFPA–54, Chapter 10
(1) Revise NFPA–54 section 10.5.4.2 by adding a second 

exception as follows:

Existing chimneys shall be permitted to have their use 

continued when a gas conversion burner is installed, 

and shall be equipped with a manual reset device that 

will automatically shut off the gas to the burner in the 

event of a sustained back-draft.
(2) Revise 10.8.3 by adding the following additional 

requirements:

(a) For all side-wall, horizontally vented, gas-fueled 

equipment installed in every dwelling, building, 

or structure used in whole or part for residential 

purposes, including those owned or operated by the 

Commonwealth and where the side-wall exhaust vent 

termination is less than seven (7) feet above finished 

grade in the area of the venting, including but not limited 

to decks and porches, the following requirements shall 

be satisfied.
1. INSTALLATION OF CARBON MONOXIDE

DETECTORS. At the time of installation of the side-wall, 

horizontally vented, gas-fueled equipment, the installing 

plumber or gas fitter shall observe that a hard-wired 

carbon monoxide detector with an alarm and battery 

backup is installed on the floor level where the gas 

equipment is to be installed. In addition, the installing 

plumber or gas fitter shall observe that a battery-

operated or hard-wired carbon monoxide detector 

with an alarm is installed on each additional level of 

the dwelling, building, or structure served by the side-

wall, horizontally vented, gas-fueled equipment. It shall 

be the responsibility of the property owner to secure 

the services of qualified licensed professionals for the 

installation of hard-wired carbon monoxide detectors.
a. In the event that the side-wall, horizontally vented,

gas-fueled equipment is installed in a crawl space or 

an attic, the hard-wired carbon monoxide detector with 

alarm and battery backup may be installed on the next 

adjacent floor level.
b. In the event that the requirements of this subdivision

cannot be met at the time of completion of installation, 

the owner shall have a period of thirty (30) days to 

comply with the above requirements, provided, however, 

that during said thirty (30) day period, a battery-

operated carbon monoxide detector with an alarm shall 

be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.

Each carbon monoxide detector as required in 

accordance with the above provisions shall comply with 

NFPA 720 and be ANSI/UL 2034-listed and IAS-certified. 

3. SIGNAGE. A metal or plastic identification plate

shall be permanently mounted to the exterior of the 

building at a minimum height of eight (8) feet above 

grade directly in line with the exhaust vent terminal for 

the horizontally vented, gas-fueled heating appliance 

or equipment. The sign shall read, in print size no less 

than one-half (1/2) inch in size, “GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. INSPECTION. The state or local gas inspector of the

side-wall, horizontally vented, gas-fueled equipment 

shall not approve the installation unless, upon 

inspection, the inspector observes carbon monoxide 

detectors and signage installed in accordance with the 

provisions of 248 CMR 5.08 (2)(a)(1 through 4). 
(b) EXEMPTIONS: The following equipment is exempt 

from 248 CMR 5.08 (2)(a)(1 through 4): 
1. The equipment listed in Chapter 10 entitled

“Equipment Not Required To Be Vented” in the most 

current edition of NFPA 54 as adopted by the Board, 

and 
2. Product-approved side-wall, horizontally vented,

gas-fueled equipment installed in a room or structure 

separate from the dwelling, building, or structure used in 

whole or in part for residential purposes. 
(c) MANUFACTURER REQUIREMENTS – GAS 

EQUIPMENT VENTING SYSTEM PROVIDED. When 

the manufacturer of product-approved side-wall, 

horizontally vented, gas-fueled equipment provides a 

venting system design or venting system components 

with the equipment, the instructions provided by the 

manufacturer for installation of the equipment and the 

venting system shall include:
1. Detailed instructions for the installation of the venting

system design or the venting system components; and
2. A complete parts list for the venting system design or

venting system. 
(d) MANUFACTURER REQUIREMENTS – GAS 

EQUIPMENT VENTING SYSTEM NOT PROVIDED. 

When the manufacturer of product-approved side-

wall, horizontally vented, gas-fueled equipment does 

not provide the parts for venting the flue gases, but 

identifies “special venting systems,” the following 

requirements shall be satisfied by the manufacturer:
1. The referenced “special venting systems” instructions

shall be included with the appliance or equipment 

installation instructions, and 
2. The “special venting systems” shall be product-

approved by the Board, and the instructions for that 

system shall include a parts list and detailed installation 

instructions. 
(e) A copy of all installation instructions for all 

product-approved side-wall, horizontally vented, 

gas-fueled equipment, all venting instructions, all 

parts lists for venting instructions, and/or all venting 

design instructions shall remain with the appliance or 

equipment at the completion of the installation. 

Sold by www.GadgetsGo.com Authorized Dealer

Summary of Contents for Rheem EcoSense RTGH-95DVN

Page 1: ...njury or property damage For Your Safety Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance To do so may result in an explosion or fire I...

Page 2: ...hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER WARNING CAUTION or NOTICE 2 These words mean IMPORTANT SAFETY INFORMATIO...

Page 3: ...emely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere in the vicinity of a water heater or any other appliance Be sure to read and follow the labels...

Page 4: ...the frozen water or the water heater may not work properly NOTICE The factory setting allows operating temperatures between 100 F 38 C and 120 F 49 C Temperatures of 85 F 29 C and up to 140 F 60 C ca...

Page 5: ...ot physically be able to smell or recognize this odorant If you are unsure or unfamiliar with the smell of natural gas or LP ask the gas supplier Other conditions such as odorant fade which causes the...

Page 6: ...all electric power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the OFF position 5 Wait five 5 minutes to...

Page 7: ...ervice personnel Make certain the power to the water heater is OFF before removing the unit cover panel Exposed electrical components and moving parts can cause personal injuries For your safety DO NO...

Page 8: ...ter heater is properly installed in accordance with local codes and the provided installation instructions Do not attempt to repair or replace any part of your water heater unless it is specifically r...

Page 9: ...1 2 140 mm 61 8 156 mm 21 8 54 mm 37 8 98 mm 27 8 73 mm 41 8 105 mm 91 2 241 mm 11 2 38 mm Specifications Direct Vent Models 177 8 454 mm 185 8 473 mm 275 8 702 mm 93 4 248 mm 21 4 59 mm 51 2 140 mm 6...

Page 10: ...over Rating gal hr 178 226 Shipping Weight lbs 81 81 Minimum Activation Flow Rate gpm 0 40 0 40 Extinction Flow Rate gpm 0 25 0 25 Hot Water Capacity gpm 35 F rise 8 5 9 5 Hot Water Capacity 77 F rise...

Page 11: ...er Faucet s Drain Valve Water Filter Cold Water Supply Shut Off Valve Note A flexible drain tube can be used To Suitable Drain To Suitable Drain Power Supply Cord Union Union Manual Gas Supply Line Sh...

Page 12: ...Off Valve Manual Gas Shut Off Valve Cap Sediment Trap Service Valve Relief Valve Relief Valve Note A flexible drain tube can be used To Suitable Drain To Suitable Drain Condensate Pipe This water heat...

Page 13: ...ldren disabled and elderly are at highest risk of being scalded See instruction manual before setting temperature at water heater Feel water before bathing or showering Temperature limiting valves are...

Page 14: ...with a small water flow Increase the water flow and recheck If it still does not operate with the hot water faucet completely open increase the temperature setting on the remote control Water Heater F...

Page 15: ...ethods Do not operate without the condensate collector drain connected and routed to the proper drain This could cause the system to malfunction or fail On a regular basis inspect the condensate drain...

Page 16: ...ucet While the water heater is operating inspect the main burner flames through the burner sight glass The flames should be blue when the main burner is firing NOTICE If the flames are not blue or you...

Page 17: ...power supply disconnected Vacuum around the water heater to remove any dust dirt and or lint buildup Clean the water heater and the remote control with a damp soft cloth and mild detergent Gently wip...

Page 18: ...the water filter under running water To remove severe sediment and dirt use a soft brush CAUTION Do not overtighten the water filter Overtightening can deform and or damage the filter Replace the filt...

Page 19: ...have drained release the lever handle to close the valve and stop draining NOTICE If the pressure relief valve on the hot water heater discharges periodically this may indicate a problem in the water...

Page 20: ...supply at the circuit breaker box Open all hot water faucets Run the water until it is COLD then shut off the faucet Close the water shut off valve Using a suitable container to catch the water remove...

Page 21: ...il this water is thawed To put the water heater back in service Disconnect drain hose Make sure the drain valve is closed Reinstall the water filter in the base of the cold water inlet line Open the w...

Page 22: ...an ambient temperature of approximately 30 F 34 C These temperatures are all based on temperatures without wind The heater only protects the internal components of the water heater NOTICE Unplugging...

Page 23: ...enough or no hot water 1 Unit is not ON 1 Turn on the unit by pressing the POWER ON OFF button 2 Water shut off valve is not completely opened 2 Check shut off valve and open completely 3 Hot water fa...

Page 24: ...one of the hot water fixtures 4 Contact a dealer or a qualified service technician Water too hot 1 Temperature is set too high 1 Decrease the temperature setting at the remote control 2 Water shut of...

Page 25: ...y devices Refer repairs to a qualified service technician When an error code is displayed Turn off all the hot water faucets Turn off the water heater by pressing the POWER ON OFF button on the remote...

Page 26: ...while but contact a dealer or qualified service technician 93 The neutralizer must be replaced The unit cannot be used until the neutral izer is replaced Contact a dealer or quali fied service technic...

Page 27: ...INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR Installation Sold by www GadgetsGo com Authorized Dealer...

Page 28: ...e used or stored Such liquids include gasoline LP gas butane or propane paint adhesives and their thinners solvents or removers Flammable vapors carry long distances from where they are used or stored...

Page 29: ...ion are as follows 1 2 in 1 3 cm for sides 0 in 0 cm for rear with support bracket s 12 in 30 cm from the bottom top and front 12 min 300 mm 12 min 300 mm 1 2 min 13 mm 12 min 300 mm 0 0 mm 0 min 0 mm...

Page 30: ...any of the following locations beauty shops dry cleaning establishments photo processing labs and storage areas for liquid and powdered bleaches or swimming pool chemicals These locations often contai...

Page 31: ...Water Heater Venting Required To Hot Water Faucet s Drain Valve Wall Plate Water Filter Cold Water Supply Shut Off Valve Power Supply Cord Union Union Union Manual Gas Supply Line Shut Off Valve Down...

Page 32: ...ater Supply Shut Off Valve Hard Wire Union Manual Gas Supply Line Shut Off Valve Flue Terminal Cap Sediment Trap Manual Gas Shut Off Valve Water Filter Union Union Service Valve Service Valve Relief V...

Page 33: ...o dry wall or concrete wall use drywall anchors or lag bolts Make sure the proper electrical outlet or supply 120 VAC 60 Hz is available and located near the unit Direct vent models come with a 6 ft 1...

Page 34: ...e material Use only 2 or 3 inch diameter pipe Refer to local codes for restrictions on the use of PVC CPVC or ABS pipe and fittings All exhaust venting materials for product installed in Canada must m...

Page 35: ...gh inspection of the existing venting and air intake system must be performed prior to any installation work Verify that the correct materials vent lengths and terminal locations as described in this...

Page 36: ...in accordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be permanently mounted to the e...

Reviews: