background image

34

INSTALLATION INSTRUCTIONS

Venting for Direct-Vent Water Heater

DANGER:

 Failure to properly vent

the water heater to the outdoors as outlined in 

this Venting section will result in death or serious 

personal injury. To avoid the risk of fire, explosion, 

or asphyxiation from carbon monoxide, NEVER 

operate the water heater unless it is properly 

vented and has adequate air supply for proper 

operation as outlined in this Venting section.

WARNING: 

Refer to page 29 for required clearances to 

combustible materials. Improper clearances can 

cause explosion or fire resulting in death, personal 

injury, and/or product damage.

CAUTIONS:

•  Check to make sure flue gases do not recirculate

into the air intake terminal when using direct

venting. If the water heater is having service issues,

flue recirculation may be a contributing factor.

•  Even when the minimum vent terminal separation

distances are followed, recirculation may still

occur depending upon the location outside

the building, the distance from other buildings,

proximity to corners, weather conditions, wind

patterns, and snow depth.

•  Periodically check to make sure that flue

recirculation is not occurring. Signs of flue gas

recirculation include frosted or frozen intake

terminals and condensate in the intake terminal

and venting system.

•  Correction to flue recirculation may involve

angling the intake away from the exhaust

terminal and increasing the distance between

them. Check to be sure the intake and exhaust

terminals are not obstructed, especially during

periods of below-freezing weather.

Venting Requirements

The installation of venting must comply with 

national codes, local codes, and the vent 

manufacturer’s instructions.
The vent exhaust and air intake must be vented 

outside as described in these instructions. DO NOT 

vent this water heater through a chimney. It must be 

vented separately from all other appliances.

NOTICE:

 The unit can be vented using

only the following recommended pipe material. 
Use only 2- or 3-inch diameter pipe. Refer to local 

codes for restrictions on the use of PVC, CPVC, or 

ABS pipe and fittings. All exhaust venting materials 

for product installed in Canada must meet ULC-S636. 
Acceptable materials or equivalent:
PVC (Schedule 40, ASTM D-1785)

CPVC (Schedule 40, ASTM F-441)

ABS (Schedule 40, ASTM D-2661) (Not permitted 

in Canada)
The fittings, other than the VENT TERMINAL, 

should be equivalent to the following:
PVC (Schedule 40 DWV, ASTM D-2665)

CPVC (Schedule 40 DWV, ASTM F-438)

ABS (Schedule 40 DWV, ASTM D-2661) (Not 

permitted in Canada)

Polypropylene

Category III Stainless Steel
DO NOT USE Schedule 20, Cell Core, Drain Pipe, 

Galvanized, Aluminum, or B-Vent.

Recommended Vent Lengths

Before starting the vent installation, careful 

planning should be given to the routing and 

termination of the vent pipes. The length of the 

vent pipes (inlet and outlet) should be kept to a 

minimum. Also, see pages 37–38 and 44 for vent 

terminal placement. Refer to the maximum and 

minimum vent length charts for the pipe sizes that 

can be used and the total equivalent length of pipe 

that can be used. Do not exceed equivalent length 

of pipe in maximum vent length chart.

Maximum Vent Length (intake/outlet):

Number 

of 90° 

Elbows

Maximum 

Length of 2" 

Straight Pipe

Maximum 

Length of 3" 

Straight Pipe

0 or 1

5.0 ft. (1.5 m)

38.0 ft. (11.6 m)

2

3.5 ft. (1.0 m)

36.5 ft. (11.1 m)

3

2.0 ft. (0.6 m)

35.0 ft. (10.6 m)

4

Not available

33.5 ft. (10.2 m)

5

Not available

32.0 ft. (9.8 m)

6

Not available

30.5 ft. (9.3 m)

The system will not operate if there is excessive 

restriction (pressure drop) in the venting system. 

Use the chart above to calculate the maximum 

pipe run length with the required number of 

elbows (e.g., a maximum 38 ft. [12 m] of 3" vent 

pipe may be used provided there is only one 90° 

elbow in the system).
A 90° elbow is equivalent to 1 ft. 6 in. (0.5 m) of 

straight pipe. 
The vent termination does not count as part of the 

straight pipe equivalent when determining the total 

vent length. 

Minimum Vent Length:

Number 

of 90° 

Elbows

Minimum 

Length of 2" 

Straight Pipe

Minimum 

Length of 3" 

Straight Pipe

1

1.0 ft. (0.3 m)

1.0 ft. (0.3 m)

Venting

Sold by www.GadgetsGo.com Authorized Dealer

Summary of Contents for Rheem EcoSense RTGH-95DVN

Page 1: ...njury or property damage For Your Safety Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance To do so may result in an explosion or fire I...

Page 2: ...hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER WARNING CAUTION or NOTICE 2 These words mean IMPORTANT SAFETY INFORMATIO...

Page 3: ...emely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere in the vicinity of a water heater or any other appliance Be sure to read and follow the labels...

Page 4: ...the frozen water or the water heater may not work properly NOTICE The factory setting allows operating temperatures between 100 F 38 C and 120 F 49 C Temperatures of 85 F 29 C and up to 140 F 60 C ca...

Page 5: ...ot physically be able to smell or recognize this odorant If you are unsure or unfamiliar with the smell of natural gas or LP ask the gas supplier Other conditions such as odorant fade which causes the...

Page 6: ...all electric power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the OFF position 5 Wait five 5 minutes to...

Page 7: ...ervice personnel Make certain the power to the water heater is OFF before removing the unit cover panel Exposed electrical components and moving parts can cause personal injuries For your safety DO NO...

Page 8: ...ter heater is properly installed in accordance with local codes and the provided installation instructions Do not attempt to repair or replace any part of your water heater unless it is specifically r...

Page 9: ...1 2 140 mm 61 8 156 mm 21 8 54 mm 37 8 98 mm 27 8 73 mm 41 8 105 mm 91 2 241 mm 11 2 38 mm Specifications Direct Vent Models 177 8 454 mm 185 8 473 mm 275 8 702 mm 93 4 248 mm 21 4 59 mm 51 2 140 mm 6...

Page 10: ...over Rating gal hr 178 226 Shipping Weight lbs 81 81 Minimum Activation Flow Rate gpm 0 40 0 40 Extinction Flow Rate gpm 0 25 0 25 Hot Water Capacity gpm 35 F rise 8 5 9 5 Hot Water Capacity 77 F rise...

Page 11: ...er Faucet s Drain Valve Water Filter Cold Water Supply Shut Off Valve Note A flexible drain tube can be used To Suitable Drain To Suitable Drain Power Supply Cord Union Union Manual Gas Supply Line Sh...

Page 12: ...Off Valve Manual Gas Shut Off Valve Cap Sediment Trap Service Valve Relief Valve Relief Valve Note A flexible drain tube can be used To Suitable Drain To Suitable Drain Condensate Pipe This water heat...

Page 13: ...ldren disabled and elderly are at highest risk of being scalded See instruction manual before setting temperature at water heater Feel water before bathing or showering Temperature limiting valves are...

Page 14: ...with a small water flow Increase the water flow and recheck If it still does not operate with the hot water faucet completely open increase the temperature setting on the remote control Water Heater F...

Page 15: ...ethods Do not operate without the condensate collector drain connected and routed to the proper drain This could cause the system to malfunction or fail On a regular basis inspect the condensate drain...

Page 16: ...ucet While the water heater is operating inspect the main burner flames through the burner sight glass The flames should be blue when the main burner is firing NOTICE If the flames are not blue or you...

Page 17: ...power supply disconnected Vacuum around the water heater to remove any dust dirt and or lint buildup Clean the water heater and the remote control with a damp soft cloth and mild detergent Gently wip...

Page 18: ...the water filter under running water To remove severe sediment and dirt use a soft brush CAUTION Do not overtighten the water filter Overtightening can deform and or damage the filter Replace the filt...

Page 19: ...have drained release the lever handle to close the valve and stop draining NOTICE If the pressure relief valve on the hot water heater discharges periodically this may indicate a problem in the water...

Page 20: ...supply at the circuit breaker box Open all hot water faucets Run the water until it is COLD then shut off the faucet Close the water shut off valve Using a suitable container to catch the water remove...

Page 21: ...il this water is thawed To put the water heater back in service Disconnect drain hose Make sure the drain valve is closed Reinstall the water filter in the base of the cold water inlet line Open the w...

Page 22: ...an ambient temperature of approximately 30 F 34 C These temperatures are all based on temperatures without wind The heater only protects the internal components of the water heater NOTICE Unplugging...

Page 23: ...enough or no hot water 1 Unit is not ON 1 Turn on the unit by pressing the POWER ON OFF button 2 Water shut off valve is not completely opened 2 Check shut off valve and open completely 3 Hot water fa...

Page 24: ...one of the hot water fixtures 4 Contact a dealer or a qualified service technician Water too hot 1 Temperature is set too high 1 Decrease the temperature setting at the remote control 2 Water shut of...

Page 25: ...y devices Refer repairs to a qualified service technician When an error code is displayed Turn off all the hot water faucets Turn off the water heater by pressing the POWER ON OFF button on the remote...

Page 26: ...while but contact a dealer or qualified service technician 93 The neutralizer must be replaced The unit cannot be used until the neutral izer is replaced Contact a dealer or quali fied service technic...

Page 27: ...INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR Installation Sold by www GadgetsGo com Authorized Dealer...

Page 28: ...e used or stored Such liquids include gasoline LP gas butane or propane paint adhesives and their thinners solvents or removers Flammable vapors carry long distances from where they are used or stored...

Page 29: ...ion are as follows 1 2 in 1 3 cm for sides 0 in 0 cm for rear with support bracket s 12 in 30 cm from the bottom top and front 12 min 300 mm 12 min 300 mm 1 2 min 13 mm 12 min 300 mm 0 0 mm 0 min 0 mm...

Page 30: ...any of the following locations beauty shops dry cleaning establishments photo processing labs and storage areas for liquid and powdered bleaches or swimming pool chemicals These locations often contai...

Page 31: ...Water Heater Venting Required To Hot Water Faucet s Drain Valve Wall Plate Water Filter Cold Water Supply Shut Off Valve Power Supply Cord Union Union Union Manual Gas Supply Line Shut Off Valve Down...

Page 32: ...ater Supply Shut Off Valve Hard Wire Union Manual Gas Supply Line Shut Off Valve Flue Terminal Cap Sediment Trap Manual Gas Shut Off Valve Water Filter Union Union Service Valve Service Valve Relief V...

Page 33: ...o dry wall or concrete wall use drywall anchors or lag bolts Make sure the proper electrical outlet or supply 120 VAC 60 Hz is available and located near the unit Direct vent models come with a 6 ft 1...

Page 34: ...e material Use only 2 or 3 inch diameter pipe Refer to local codes for restrictions on the use of PVC CPVC or ABS pipe and fittings All exhaust venting materials for product installed in Canada must m...

Page 35: ...gh inspection of the existing venting and air intake system must be performed prior to any installation work Verify that the correct materials vent lengths and terminal locations as described in this...

Page 36: ...in accordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be permanently mounted to the e...

Reviews: