0787-1216
Properties
Product manual | Version: 1.0.0
19
Compact Power Supply
0
t [ms]
max
I
off
t
on
t
OUT [A]
I
Figure 9: Hiccup Mode
Input
Voltage
Output
Voltage
Switch-on Time
Figure 10: Turn-on Time
!
NOTICE
Select conductor cross-sections according to current load!
In the event of a fault, the output current of a power supply can be up to 1.5 × I
OUT
. Only
use conductor cross-sections sufficient for the current load!
Table 15: Technical Data – Output Side Connection
Property
Value
Connection Technology
Spring pressure connection technology (pico-
MAX® 5.0, 4-pole)
Cross-section
Solid
0.2 … 2.5 mm² / 24 … 12 AWG
Fine-stranded
0.2 … 2.5 mm² / 24 … 12 AWG
Insulated ferrule with plastic collar
0.25 … 1.5 mm² / 23 … 16 AWG
Ferrule without plastic collar
0.25 … 2.5 mm² / 23 … 12 AWG
Strip Length
9 … 10 mm / 0.35 … 0.39 inch
Required tools (conductor termination)
Operating tool, type 1 (see
8