26
Device Description
EPSITRON® COMPACT Power
787-1202 / -1212 / -1216 / -1226 EPSITRON® COMPACT Power
Manual
Version 1.0.0
Table 11: Electrical Data 787-1202 / 787-1212
787-1202
787-1212
Recommended external fuse
Miniature circuit
breaker 6 A (C
characteristic), 10 A (B
characteristic) or
higher.
An external DC fuse is
required for the DC
input voltage.
Miniature circuit
breaker 6 A (C
characteristic), 10 A (B
characteristic) or
higher.
An external DC fuse is
required for the DC
input voltage.
Safety and Protection
Test voltage Primary‒Secondary
3 kV AC
3 kV AC
Protection class
II
II
Overvoltage protection
≤ 31 V
≤ 31 V
Short-circuit protected
Yes
Yes
No-load-proof
Yes
Yes
Maximum feedback voltage
35 VDC
35 VDC
Parallel connection
Yes
Yes
Series connection
Yes
Yes
MTBF acc. to IEC 61709
> 700000 h
> 500000 h
General
Degree of pollution
2 (acc. to EN 50178)
2 (acc. to EN 50178)
1)
see section “Notes on Operation” > “Derating”