28
Device Description
EPSITRON® COMPACT Power
787-1202 / -1212 / -1216 / -1226 EPSITRON® COMPACT Power
Manual
Version 1.0.0
Table 12: Electrical Data 787-1216 / 787-1226
787-1216
787-1226
Recommended external fuse
Miniature circuit
breaker 6 A (C
characteristic), 10 A (B
characteristic) or
higher.
An external DC fuse is
required for the DC
input voltage.
Miniature circuit
breaker 6 A (C
characteristic), 10 A (B
characteristic) or
higher.
An external DC fuse is
required for the DC
input voltage.
Safety and Protection
Test voltage Primary–Secondary 3 kV AC
3 kV AC
Protection class
II
II
Overvoltage protection
≤ 31 V
≤ 31 V
Short-circuit protected
Yes
Yes
No-load-proof
Yes
Yes
Maximum feedback voltage
35 VDC
35 VDC
Parallel connection
Yes
Yes
Series connection
Yes
Yes
MTBF acc. to IEC 61709
> 500000 h
> 500000 h
General
Degree of pollution
2 (acc. to EN 50178)
2 (acc. to EN 50178)
1)
see section “Notes on Operation” > “Derating”
Pos: 35.4 /Serie 787 (
EPSITRON
)/Ger ätebeschrei bung/T echnische D aten/Angaben zur Ver drahtung Ver drahtung 787- 12xx @ 19\mod_1397739135513_21.docx @ 152098 @ @ 1
Table 13: Wiring
Input Side
Output Side
Connection Technology
Spring pressure
connection technology
(
picoMAX
®
5.0)
Spring pressure
connection technology
(
picoMAX
®
5.0)
Cross section
0.2 mm² … 2.5 mm² / AWG 24 … 12
Strip length
9 mm … 10 mm / 0.35 in … 0.39 in
Pos: 35.5 /Serie 787 (
EPSITRON
)/Wichtige Erläuterungen/Sicher heits- und sonstige Hi nweise/Achtung/Achtung: Leiterquerschnitte entspr echend der Strombelastung wähl en! @ 18\mod_1393411327873_21.docx @ 146540 @ @ 1
Select conductor cross sections as required for current load!
In the event of a fault, the output current of a power supply can be up to 2 × I
OUT
.
Only use conductor cross sections designed for this current load.
Pos: 35.6 /Serie 787 (
EPSITRON
)/Ger ätebeschrei bung/T echnische D aten/Angaben zu U mg ebungsbedi ngungenU mgebungsbedi ngungen 787-12xx (VS) @ 18\mod_1393410674974_21.docx @ 146534 @ @ 1