![WAGO 762-5/8000-000 Series Manual Download Page 68](http://html1.mh-extra.com/html/wago/762-5-8000-000-series/762-5-8000-000-series_manual_3153253068.webp)
68 Connecting
Touch Panel Advanced Line
762-5xxx/8000-000x TP 600
Manual
Version 1.3.0
7
Connecting
7.1
Connection Example
Figure 21: Connection Example
7.2
Earthing
Earthing is performed via connector X5, pin 3 “FE” (functional earth) and via the
earthing screw or lug on the rear.
For this, use the included 734-103 Female Connector featuring three CAGE
CLAMP
®
connections. First, open CAGE CLAMP
®
no. 3 using an operating tool.
Then insert the conductor (strip length: 7 mm, max. 1.5 mm²) and remove the
tool.
Plug the female connector into the X5 connector and then verify that the
clamping connection is secured.
7.3
Connecting Devices
Peripherals are connected electrically by the interfaces on the bottom and left
side.
The
ETHERNET interfaces
are used to connect to a LAN or to the Internet for
communication with the controller. Crossover or patch cables category 5e can be
used.
The
USB 2.0 interfaces
can be used to connect a keyboard or mouse as an
alternative input device. Also, up to 2 USB memory devices can be connected.
Because there are a large number of USB devices on the market, no guarantee
can be made about the function of individual devices.
USB devices must be connected before power ON because they are not hot-
pluggable.