Touch Panel Advanced Line
Visualization 185
762-5xxx/8000-000x TP 600
Manual
Version 1.3.0
9.5.2.3 Frame Objects
If you use frame objects together with pointer instruments or bar graphs in your
e!
COCKPIT
project, it is recommended to delete the “Color Variables > Color
Change” setting in the frame object properties. This also positively affects the
refresh rate.
You can also disable the option in the
e!
COCKPIT
project under “CODESYS
Options > Visualization > Edit Options” by disabling the checkbox “Link to
Switching/Key Variable”. When creating new visualization objects, the option is
not set by default.
9.5.2.4 Visualization Style
If you use only visualizations with a fixed resolution in your project, it is
recommended to use a visualization style in version 3.5.3.0. These visualization
styles can be processed faster from a panel. The visualization style can be
changed in the program structure in the “Visualization Manager” in the “Settings”
tab. If you use these visualization styles in the “Isotropic” or “Anisotropic” scaling
options, it may adversely affect the quality of the graphical representation.
9.5.2.5 URL Configuration
If you do not use communication encryption in your application (see also section
“Response Time”), communication via http is recommended from the standpoint
of response time. In this case, please use the following URL for a WAGO
controller:
http://<IP address or name of the WAGO controller>:8080/webvisu.htm
9.5.2.6 Task Configuration of the WAGO Controller
The response time of the
e!
RUNTIME
Web visualization largely depends on the
control program, which is processed on the WAGO controller since user input is
processed on the WAGO controller. Therefore, as long as the control application
allows it, the priority of the “VISU_TASK” should be placed in the priority range 4
... 14. The cycle time of the “VISU_TASK” should be as short as possible,
typically in the range of 25 ms ... 100 ms.
9.5.3
HTML5 Web Visualizations
When creating a Web visualization based purely on HTML5 and not on
CODESYS, it is important to know the HTML5 capabilities of the integrated Web
browser to ensure that the visualization can be displayed properly.
The panels use the “Qt WebEngine” of “Qt 5.9.4” Web browser.
You can obtain detailed information at
https://html5test.com/s/2abdf228f6dd0bc7.html
graphics, etc. are available to you when planning your HTML5 Web visualization.
Use only these elements to ensure the visualization is properly displayed.
In the Web browser, not all elements of the ECMA5 standard are available. E.g.
the function bind() is missing. If possible, you can add this function in your
Summary of Contents for 762-5/8000-000 Series
Page 1: ...Manual Touch Panel Advanced Line 762 5xxx 8000 000x TP 600 WAGO Touch Panel Version 1 3 0...
Page 12: ...12 Regulations Touch Panel Advanced Line 762 5xxx 8000 000x TP 600 Manual Version 1 3 0...
Page 63: ...Touch Panel Advanced Line Functions 63 762 5xxx 8000 000x TP 600 Manual Version 1 3 0 Browser...