background image

68 

Parameterizing 

WAGO-TO-PASS® 761 

 

 

761-214 Telecontrol Module Compact, 8 AI, ESP, DSP 

 

Manual 

 

Version 2.0.0  

  

7.6 

Configuring Error Detectors 

The 

TO-PASS

®

 telecontrol module can transmit error messages to a maximum of 

four recipients. The recipients are informed either directly one after another or (if 
configured) after expiration of the time delay for acknowledgment. The message 
is sent by the 

TO-PASS

®

 telecontrol module as an SMS; however, it can also be 

sent as an e-mail, fax or voice mail. In addition, the error messages can also be 
transmitted to a Web portal. 

 

 

 

Device-dependent Function 

Devices with GPRS functionality (device identifier "Web") are required to 
transmit error messages to a Web portal. 

 

 

 

 

Note the calculation packet size! 

Please note the information given on calculation packet size in the Section 
"Important Information - Rounding of Blocks for GPRS Links." 

 

  

7.6.1 

Alarm Messages for Digital Inputs 

If on or off states of digital inputs are to be sent as error messages, select the 
desired recipient for the respective input statuses using buttons 

[1]

 ... 

[4].

 Click 

the 

[Internet]

 button to also transmit the message to a Web portal.  

In addition, you can also specify the analog values that are to be transmitted along 
with the error message. 

  

7.6.2 

Limit Messages for Counter Inputs 

If violations of upper/lower counter limits are to be sent as error messages, 
activate the respective counter value and select the desired recipient using buttons 

[1]

 ... 

[4]

.  

Click the 

[Internet]

 button to also transmit the message to a Web portal.  

 
You can also specify the analog values that are to be transmitted along with the 
error message. 

  

7.6.3 

Limit Messages for Analog Inputs 

You can specify a maximum of 2 limit values for every analog input for which 
(upper/lower) limit value violations are to be sent as error messages.  
Enter the desired value and select whether the error message is to be sent for 
violation of the upper or lower limit value using the buttons [

increasing] 

or 

[

decreasing]

.  

Select the desired recipient for the respective limit value using the buttons 

[1] … 

Summary of Contents for 761-214

Page 1: ...Manual WAGO TO PASS 761 Telecontrol Module Compact 8 AI ESP DSP 761 214 Telecontrol module for fault detection indication monitoring and remote control Version 2 0 0...

Page 2: ...49 0 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never b...

Page 3: ...h Open Source GPL 11 2 4 Block Rounding for GPRS Connections 11 2 5 Safety Advice Precautions 12 3 Device Description 15 3 1 Scope of Delivery 15 3 2 Use 15 3 3 View 17 3 4 Connectors 18 3 4 1 Antenna...

Page 4: ...Measurement 41 5 2 4 Digital Outputs 42 5 2 5 Analog Outputs 43 5 2 5 1 Current Measurement 43 5 2 5 2 Voltage Measurement 44 6 Commissioning 45 6 1 Installing the Operating Software 45 6 2 Starting t...

Page 5: ...2 1 1 Setting or Resetting a Digital Output 84 8 2 1 2 Setting an Analog Output 85 8 2 1 3 Changing the Counter Value or Status 86 8 2 2 Telecontrol with the TO PASS Operator Program 87 8 2 2 1 Inputs...

Page 6: ...ions are included if applicable 1 1 Validity of this Documentation This documentation is only applicable to the telecontrol module 761 214 Telecontrol Module Compact 8 AI ESP DSP 1 2 Copyright This Ma...

Page 7: ...dicates a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation which if not a...

Page 8: ...umentation WAGO TO PASS 761 761 214 Telecontrol Module Compact 8 AI ESP DSP Manual Version 2 0 0 Additional Information Refers to additional information which is not an integral part of this documenta...

Page 9: ...d data files are marked in italic type e g C Programme WAGO I O CHECK Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a menu item from...

Page 10: ...in automation The specialists must be familiar with the current norms and guidelines for the devices and automated environments All changes to the controller should always be carried out by qualified...

Page 11: ...Open Source GPL The TO PASS Compact telecontrol module firmware contains Open Source software under GPL According to Section 3b of GPL we offer you the source code You can obtain the source code with...

Page 12: ...tallation repair or maintenance work Installation only in appropriate housings cabinets or in electrical operation rooms TO PASS telecontrol modules are exposed operating equipment They may only be as...

Page 13: ...dBi Only qualified staff can install and maintain the TO PASS remote module and its antenna The transmitted must be off when working on or nearer to the antenna than specified below HF Exposition The...

Page 14: ...s in an enclosure being resistant to the above mentioned materials Clean tools and materials are imperative for handling devices modules Cleaning only with permitted materials Clean soiled contacts us...

Page 15: ...le for the connection of signals from plants transmission preparation of values for the operator TO PASS telecontrol modules 761 214 may be used as fault indicator remote data request system data memo...

Page 16: ...version Standard Extended Extended Parameterizable Time request script Not implemented Not implemented Not implemented Implemented Counter inputs Not supported Not supported Not supported Supported De...

Page 17: ...14 Telecontrol Module Compact 8 AI ESP DSP Manual Version 2 0 0 3 3 View Figure 1 Front view Position Description 1 SIM Card insert 2 Antenna connection 3 Statusindication 4 PC interface 5 Connecting...

Page 18: ...nnectors 3 4 1 Antenna The screw connector SMA socket for the GSM antenna is located at the top of the housing Figure 2 Antenna connection Observe the maximum length of the antenna cable The total len...

Page 19: ...source LPS requirements per DIN EN 60950 1 Table 4 Terminal assignment for operating voltage Figure 3 Terminal assignment for operating voltage Connection Short name Designation 1 2 Uv Operating volta...

Page 20: ...s constructively no direct conduction connection between the cabinet frame or machine parts and the carrier rail Here the earth ground must be set up via an electrical conductor accordingly valid nati...

Page 21: ...To achieve this connect the shield over a large surface area e g WAGO shield connecting system This is especially recommended for large scale systems where equalizing current or high impulse type cur...

Page 22: ...4 4 WAGO Shield Connecting System The WAGO shield connecting system consists of shield clamping saddles busbars and various mounting carriers to enable a wide variety of setups For more information on...

Page 23: ...puts Figure 5 Terminal assignment for digital inputs Connection Short name Designation 5 DI1 Digital input 1 6 DI2 Digital input 2 7 DI3 Digital input 3 8 DI4 Digital input 4 9 DI5 Digital input 5 10...

Page 24: ...er inputs Table 7 Counter input pin assignments Figure 6 Counter input pin assignments Connection Short name Explanation 5 DI1 Counter input 1 configurable 6 DI2 Counter input 2 configurable 7 DI3 Cou...

Page 25: ...puts Figure 7 Terminal assignment for analog inputs Connection Short name Designation 13 AI1 Analog input 1 14 AI1 Analog input 1 15 AI2 Analog input 2 16 AI2 Analog input 2 17 AI3 Analog input 3 18 A...

Page 26: ...2 0 0 Analog inputs are single ended The analog inputs are single ended and the Aix connections are connected internally to the GND connections Connect shielding Shielded cables are required for analo...

Page 27: ...ELV voltages Only SELV PELV voltages shall be connected to the device terminals Table 9 Terminal assignment for digital outputs Figure 8 Terminal assignment for digital outputs Connection Short name D...

Page 28: ...rminals Table 10 Terminal assignment for analog outputs Figure 9 Terminal assignment for analog outputs Connection Short name Designation 29 AO1 Analog output 1 30 AO1 Analog output 1 31 AO2 Analog ou...

Page 29: ...ace Pin Description 1 Not assigned 2 TXD 3 RXD 4 Not assigned 5 GND 6 Not assigned 7 Not assigned 8 Not assigned 9 Not assigned Table 12 PC interface cable assignment WAGO TO PASS PC D Sub 9 Pin Descr...

Page 30: ...odem is activated Initialization takes approx 40 s after system start up if everything is OK SMS GPRS processing Antenna is not connected the modem is searching for a network Poor GSM network the mode...

Page 31: ...AWG 14 sol Stripped length 9 mm 10 mm 3 6 2 Supply Table 15 Technical Data Supply Operating voltage 10 V 30 VDC Nominal voltage operation with mains power 24 VDC Nominal voltage operation using batter...

Page 32: ...Number of inputs 8 Input type Type 3 acc to IEC 61131 2 Input voltage 0 V 30 V DC Signal voltage 0 0 V 5 V DC Signal voltage 1 7 V 30 V DC Input current max at 30 V DC 2 9 mA 3 6 6 Counter Inputs Tab...

Page 33: ...Energy dissipation Wmax unique switching off 125 mJ Lmax 2 Wmax I2 3 6 9 Analog Outputs Table 22 Technical Data Analog Outputs Number of outputs 2 Output current 0 4 mA 20 mA Load impedance 600 Resolu...

Page 34: ...tive per Article 3 2 RoHS Device complies with European RoHS directive FCC Verification per FCC 15b Approval Canada Approval Croatia Approval Mexico Approval Turkey 3 8 Standards and Guidelines 761 21...

Page 35: ...r an ambient temperature of 20 C to 70 C In the event of higher or lower temperatures proper cooling or heating arrangements must be provided Please contact WAGO Kontakttechnik GmbH Co K G for assista...

Page 36: ...moving the TO PASS telecontrol module from the DIN rail Figure 13 Removing the TO PASS telecontrol module from the DIN rail 1 Press the undersurface against the lower DIN rail edge until the TO PASS t...

Page 37: ...one connection these must be connected in an up circuit wiring assembly for example using WAGO feed through terminals Terminate both solid and ferruled conductors without actuation by simply pushing...

Page 38: ...IN rail The shield connection of the TO PASS telecontrol module shield terminal 38 must be connected to the DIN rail The DIN rail must have a low impedance ground see section Connections Ground 5 2 1...

Page 39: ...SELV PELV voltages Only SELV PELV voltages shall be connected to the device terminals Connect shielding Shielded cables are recommended for the counter inputs When using shielded cables the shield mus...

Page 40: ...e terminals Analog inputs are single ended The analog inputs are single ended and the Aix connections are connected internally to the GND connections Connect shielding Shielded cables are required for...

Page 41: ...mer Voltage measurement cannot be performed via multiplier at the analog inputs since the internal resistance of the TO PASS telecontrol module depends on the input current WAGO 857 Series JUMPFLEX Is...

Page 42: ...214 Telecontrol Module Compact 8 AI ESP DSP Manual Version 2 0 0 5 2 4 Digital Outputs Only connect SELV PELV voltages Only SELV PELV voltages shall be connected to the device terminals Figure 18 Conn...

Page 43: ...SELV PELV voltages Only SELV PELV voltages shall be connected to the device terminals Connect shielding Shielded cables are required for analog outputs The cable shield must be connected to the groun...

Page 44: ...1 761 214 Telecontrol Module Compact 8 AI ESP DSP Manual Version 2 0 0 5 2 5 2 Voltage Measurement RL Load resistance RM Internal resistance of measuring device RL RM must be less than 600 With RM RL...

Page 45: ...lorer using a double click 5 Select the CD drive in which you have placed the CD with the operating software 6 Start the WAGO TO PASS_SETUP 2 17 EXE program or a newer version in the main directory on...

Page 46: ...he TO PASS telecontrol module it must first be configured with the telephone number 1 Every TO PASS telecontrol module requires an SIM card for proper operation You can obtain an SIM card from any mob...

Page 47: ...Use PIN button so that the TO PASS telecontrol module does not use the PIN code Also deactivate the PIN on the SIM card To do this insert the SIM card into a cell phone and under menu item Security se...

Page 48: ...nalog ISDN Select the type of connection for communicating with the TO PASS telecontrol module RS 232 Direct connection via RS 232 cable GSM Dial up using GSM modem on the PC Analog Dial up using anal...

Page 49: ...ace COM1 COMx Here select the serial interface where the communication cable is connected with a RS 232 connection Language English German French Select the langauge for the TO PASS operator interface...

Page 50: ...you have set the type of connection for communicating with the TO PASS telecontrol module you are then able to read out the parameters of the connected module Select the menu option Edit Read Paramet...

Page 51: ...le to be configured from the project tree under it select the Identity option On the right side you will find the selection field for the function the display field for the name the input field for th...

Page 52: ...ton and enter the PIN number in the field provided Roaming Roaming is always activated in TO PASS telecontrol modules To select a favorite carrier click the Allow button and enter the 5 digit carrier...

Page 53: ...ssages are sent by the TO PASS telecontrol module as SMS however they can also be sent as an e mail fax or voice mail as defined in configuration The TO PASS telecontrol module can also transmit messa...

Page 54: ...mail address e g for a T Mobile SIM card 8000 receiver provider net Transmission as fax Follow the instructions from the provider for transmissions as fax messages For T Mobile or Vodafone for exampl...

Page 55: ...er for transmitting the data of the logger APN access In this field enter the APN access point Access Point Name for the SIM card provider e g T Mobile internet t mobile Vodafone web vodafone de The s...

Page 56: ...ital Inputs Digital inputs 1 4 can be configured as counter inputs starting from Firmware Version FW 2 33 The counters count up or down from the given starting and end value With upward counting excee...

Page 57: ...n via the visualization system This function is available starting with Firmware Version FW 2 33 Starting value In this field enter the starting value for the counter This field is only active when th...

Page 58: ...or applications with GPRS transmission Analog value Use these buttons to select up to four analog values which can also be transmitted with the message when the digital input has been set or when the...

Page 59: ...ns with GPRS transmission Analog value Use these buttons to select up to four analog values which can also be transmitted with the deactivation message when the digital input has been reset or when th...

Page 60: ...e following applies in this case DI1 20 1 DI2 21 2 DI3 22 4 and DI4 23 8 Thus for example if DI1 and DI3 are set then the binary number is 5 If only DI4 is set then the binary number is 8 In the multi...

Page 61: ...ngs Enable Addresses Multiplex operation Click the button Use to enable disable multiplex operation for digital inputs DI1 DI4 If a status combination of digital inputs DI1 DI4 is fulfilled in multipl...

Page 62: ...the Multiplex Input entry The input fields for the alarm texts pertaining to the 16 statuses are provided on the right side Figure 26 Configuring multiplex operation alarm texts Table 29 Configuring m...

Page 63: ...e analog inputs Table 30 Configuring the analog inputs Standardization Input signal Use these buttons to select the input signal for the sensor connected to the TO PASS telecontrol module Min value In...

Page 64: ...g value Use these buttons to select up to four analog values which can also be transmitted with the message when the analog value has violated the first upper lower limit Second value In this field en...

Page 65: ...connects the DC voltage available at terminal 37 to the corresponding output Deactivation text In this field enter the deactivation text for the output When the TO PASS telecontrol module receives th...

Page 66: ...the output signal for the actuator connected to the TO PASS telecontrol module Min value In this field enter the starting value from which the output value is normalized This value corresponds to the...

Page 67: ...s after the decimal point are also taken into account for switching of the analog outputs A period decimal point must be used as the separator Up to four digits are evaluated With a minimum value of 0...

Page 68: ...s of digital inputs are to be sent as error messages select the desired recipient for the respective input statuses using buttons 1 4 Click the Internet button to also transmit the message to a Web po...

Page 69: ...Telecontrol Module Compact 8 AI ESP DSP Manual Version 2 0 0 4 Click the Internet button to also transmit the message to a Web portal In addition you can also specify the analog values that are to be...

Page 70: ...ASS telecontrol module waits for an acknowledgement after transmitting an alarm SMS Acknowledgement is in the form of an SMS containing the configured response text or a simple call by the recipient t...

Page 71: ...elect the TO PASS telecontrol module from the project tree using the identifier Select the entry Repeat times under the option Special Functions The input fields for the Web interval the Web outputs a...

Page 72: ...This function is available starting with Firmware Version FW 2 33 Switching input In this field select a digital input to be used for switching of the transmission interval between Web interval Off st...

Page 73: ...ain times of day Time adjustment must be performed for limited SMS transmission to check the day of the week and the active time The first SMS is transmitted when the starting value for the active tim...

Page 74: ...stment Table 35 Setting the time adjustment Settings Time adjustment The TO PASS telecontrol module sends an SMS to itself and receives the current time from the provider transmitted by this SMS when...

Page 75: ...nter the cycle time in minutes at which the process image is to be saved The process image is specific to devices and firmware used and is described in the Section Operation Data Logger DSP The data l...

Page 76: ...r you have adapted all parameters for the TO PASS telecontrol module to your requirements you have to write the parameters to the connected module Select the menu option Edit Write Parameters The soft...

Page 77: ...Module Compact 8 AI ESP DSP Manual Version 2 0 0 8 Operation 8 1 Remote Query of Process Values The TO PASS telecontrol module offers two options for remote inquiry of the process values available Que...

Page 78: ...0 not set 1 set 00 00mA Analog output 1 00 00mA Analog output 2 Normal Status Status text or prepaid information optional AC 99 Alarm counter displays the alarms that are still possible per hour The...

Page 79: ...Table 39 Counter status Status Explanation 0 Digital input not configured as a counter e ZW Counter is active Counter value d ZW Counter is not active Counter value o ZW Counter overflow Counter vlau...

Page 80: ...s values with the TO PASS operator program select the menu item Visualization Process values The program establishes a link to the TO PASS telecontrol modules selected Please note the mode used to dia...

Page 81: ...e on line display is green Figure 34 Visualization of the process values Process values pertaining to inputs are displayed in the upper portion of the window and those pertaining to digital and analog...

Page 82: ...click the Counter button possible only when inputs have been configured as counters The process values displayed are valid when the on line indicator is highlighted in green Figure 35 Counter process...

Page 83: ...SP DSP Manual Version 2 0 0 8 2 Telecontrol TO PASS telecontrol modules offer the option of influencing a process remotely with the help of their analog and digital outputs There are two methods avail...

Page 84: ...SMS containing the identifier and the transmitted text Example Table 40 Example of parameters for Set DO Parameter Setting Activation text DOUT1 1 Deactivation text DOUT1 0 Turn off time 00 00 00 Sen...

Page 85: ...O1 Parameter Setting Output Signal 0 20 mA Min value 0 Max value 100 Unit Text AOUT1 Send an SMS with the text AOUT1 75 to set analog output 1 to a value of 15 mA 75 The TO PASS telecontrol module ack...

Page 86: ...ommands for counters Control command Function Cx x 1 4 Select counter 1 4 E Activate counter D Deactivate counter R Reset counter n e g 500 Set counter value Control commands must be concluded with a...

Page 87: ...alues with the TO PASS operator program select the menu item Visualization Process values The program establishes a link to the TO PASS telecontrol modules selected Please note the mode used to dial u...

Page 88: ...puts are displayed in the upper portion of the window and those pertaining to digital and analog outputs are displayed in the lower portion of the window Digital inputs configured as counter inputs ar...

Page 89: ...ted in green Figure 37 Counter process values The counter statuses are shown at the top of the window while the counter values the starting and end values and the limits are shown at the bottom To sta...

Page 90: ...owledgement SMS containing the identifier the response text and the alarm text Acknowledgement by phone call is based on the card being used Some data cards do not allow voice links meaning that ackno...

Page 91: ...ally to the respective ready state This takes place with simple changeover via SMS To do this just send an SMS with the text Standby1 to the TO PASS telecontrol modules The TO PASS telecontrol module...

Page 92: ...ues of the data logger using the menu item Visualization Data logger Either select all inputs or only specific inputs with the help of the selection field in the upper portion of the window All entrie...

Page 93: ...I ESP DSP Manual Version 2 0 0 As an alternative you can also display all data records saved via Edit Display all data records or all new data records for the selected telecontrol module via Edit Disp...

Page 94: ...ed To read the contents of the event logger select the menu option Edit Read all data records It is possible to display all values of the event logger with the help of the menu option Visualization Ev...

Page 95: ...he outputs are displayed in the lower area By pressing the buttons Output 1 Output 4 in the upper area switch digital inputs on and off A value range of 0 mA 20 mA and 4 mA 20 mA is defined for the an...

Page 96: ...nd end values and the limits are shown at the bottom To start a counter click the button Activate To stop a counter click the button Deactivate To restore the counter to its starting value click the b...

Page 97: ...h a direct serial link to the TO PASS telecontrol module To test the connection select the menu option Edit Test SMS GPRS The following window is displayed Figure 40 Testing the connection Select the...

Page 98: ...link required The modem test may only be performed with a direct serial link to the TO PASS telecontrol module To test the mode select the menu item Modem Test The following window is displayed Figure...

Page 99: ...I1 40 Figure 17 Connection example for voltage measurement via U I converter at input AI1 41 Figure 18 Connection example for a relay at DO1 output 42 Figure 19 Connection example for a display device...

Page 100: ...32 Table 19 Technical Data Counter Inputs 32 Table 20 Technical Data Analog Inputs 32 Table 21 Technical Data Digital Outputs 33 Table 22 Technical Data Analog Outputs 33 Table 23 Technical Data Data...

Page 101: ...WAGO TO PASS 761 101 761 214 Telecontrol Module Compact 8 AI ESP DSP Manual Version 2 0 0...

Page 102: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 5 71 8 87 0 Fax 49 5 71 8 87 1 69 E Mail info wago com Internet http www wago com...

Reviews: