![WAGO 750-527 Manual Download Page 45](http://html1.mh-extra.com/html/wago/750-527/750-527_manual_3222645045.webp)
WAGO-I/O-SYSTEM 750
Use in Hazardous Environments 45
750-527 4DO 30V AC/DC 2.0A SSR
Manual
Version 1.0.0
Figure 22: Text Detail – Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Table 25: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Marking
Description
Dust
Ex
Explosion protection mark
nA
Type of protection
[ia IIIC]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
X
Symbol used to denote specific conditions of use
Gases
Ex
Explosion protection mark
nA
Type of protection
[ia Ga]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 0
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
X
Symbol used to denote specific conditions of use