750-515 4DO 250V AC 2.0A/ Relais 4NO/ Potential Free 

 

 

Manual 

 

Version 1.0.1  

 

3.5.4 

Outputs 

Table 9: Technical Data – Outputs 

No. of outputs 

4 make contacts

 

Response time 

max.

 

10 ms

 

Bounce type 

typ.

 

1 ms

 

Drop-out time 

max.

 

5 ms

 

Contact Material 

AgNi type + Au

 

Switching operation  

(mechanical life) 

min.

 

 

2 × 10

(at 180/Min.)

 

Switching operation (electrical life) 

min.

*)

  1 × 10

(3 A /  250 VAC,  30 VDC, 

resistive load) 

5 × 10

4

 (5 A /  250 VAC,  30 VDC, 

resistive load) 

Switching frequency 

max.

 

20/Min (3 A /  250 VAC,  30 VDC) 

6/Min (5 A /  250 VAC,  30 VDC)

 

*)

 Please note load limit and life cycle curves!

 

 

Pos: 18.24.1 /Alle Serien (Allgemeine M odul e)/Überschriften/Neue Ü berschriften/Ebene 3Anschlusstechni k - Überschrift 3 @ 17\mod_1380123271324_21.docx @ 132788 @  3 @ 1 

 

3.5.5 

Connection Type 

Pos: 18.24.2 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Technische D aten/T echnische D aten Verdrahtungsebene CC - 0,08 bis 2,5mm2 @ 17\mod_1380121238809_21.docx @ 132780 @  @ 1 

 

Table 10: Technical Data – Field Wiring 

Wire connection 

CAGE CLAMP

®

 

Cross section 

0.08 mm² … 2.5 mm², AWG 28 … 14 

Stripped lengths 

8 mm … 9 mm / 0.33 in 

 

Pos: 18.24.3 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Technische D aten/Anschl usstechni k/Technische Daten D atenkontakte @ 17\mod_1380123495844_21.docx @ 132794 @   @ 1 

 

Table 11: Technical Data – Data Contacts 

Data contacts 

Slide contact, hard gold plated, self-

cleaning 

 

Pos: 18.25 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Technische D aten/Klimatische U mgebungsbeding ungen/T echnische D aten Kli mat. U mgebungsbed.  ohne  erw. T emp.  0...55°C/- 25...+ 85°C @ 5\mod_1247657968368_21.docx @ 37603 @ 3 @ 1 

 

3.5.6 

Climatic Environmental Conditions 

Table 12: Technical Data – Climatic Environmental Conditions 

Operating temperature range 

0 °C … 55 °C 

Storage temperature range 

25 °C … +85 °C 

Relative humidity without condensation  Max. 95 %  

Resistance to harmful substances 

Acc. to IEC 60068-2-42 and 

IEC 60068-2-43 

Maximum pollutant concentration at 

relative humidity < 75 % 

SO

2

 

 25 ppm  

H

2

 10 ppm 

Special conditions 

Ensure that additional measures for 

components are taken, which are used in 

an environment involving:  

– dust, caustic vapors or gases  

– ionizing radiation 

 

Pos: 18.26 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx  @  21810 @   @ 1 

 

 

 

Summary of Contents for 750-515

Page 1: ...YSTEM 750 Manual 750 515 4DO 250V AC 2 0A Relais 4NO Potential Free 4 Channel Relay Output Module 250 VAC 2 0 A Potential Free 4 Make Contacts Version 1 0 1 Pos 3 Alle Serien Allgemeine M odul e Recht...

Page 2: ...Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we...

Page 3: ...Advice Precautions 11 3 Device Description 13 3 1 View 15 3 2 Connectors 16 3 2 1 Data Contacts Internal Bus 16 3 2 2 Power Jumper Contacts Field Supply 16 3 2 3 CAGE CLAMP Connectors 17 3 3 Display E...

Page 4: ...America According to NEC 500 42 7 2 Installation Regulations 43 7 2 1 Special Conditions for Safe Use T V 14 ATEX 148929 X 44 7 2 2 Special Conditions for Safe Use ATEX Certificate T V 12 ATEX 106032...

Page 5: ...50 WAGO I O SYSTEM Hi nweise zur D okumentati on Hi nweise Achtung Hinweis zur D okumentati on Buskl emmen 750 xxxx 4 mod_1237986979656_21 docx 29023 1 The I O module 750 515 shall only be installed a...

Page 6: ...injury Pos 12 5 4 All e Serien Allgemei ne Module Sicherheits und sonstige Hi nweise Vorsicht Vorsicht _War nung vor Personensch den allgemein_ Erl uterung 13 mod_1343310028762_21 docx 101038 1 Person...

Page 7: ...Relais 4NO Potential Free Manual Version 1 0 1 Additional Information Refers to additional information which is not an integral part of this documentation e g the Internet Pos 12 6 Dokumentation allg...

Page 8: ...1 5 Font Conventions Pos 12 10 Alle Serien Allgemeine M odul e Rechtliches Allgemeines Schriftkonventi onen 3 mod_1221059521437_21 docx 21714 1 Table 2 Font Conventions Font Type Indicates italic Name...

Page 9: ...rsonalqualifi kation 750 xxxx berschrift 3 und Inhalt 3 mod_1224061208046_21 docx 24063 3 1 2 1 2 Personnel Qualifications All sequences implemented on WAGO I O SYSTEM 750 devices may only be carried...

Page 10: ...stand der Ger te berschrift 3 und Inhalt 3 mod_1221060446109_21 docx 21723 3 1 2 1 4 Technical Condition of Specified Devices The devices to be supplied ex works are equipped with hardware and softwar...

Page 11: ...ied staff only by means of specific keys or tools Pos 15 10 3 Alle Serien Allgemeine D okumente Allgemeine M odul e Wichtige Erl uter ungen Sicherheitshinweise Gefahr Gefahr Unfall verh tungsvorschrif...

Page 12: ...heitshinweise Achtung Achtung Kei n Kontaktspray verwenden 6 mod_1260181290808_21 docx 46755 1 Do not use any contact spray Do not use any contact spray The spray may impair contact area functionality...

Page 13: ...GO I O SYSTEM Ger tebeschrei bung Ei nlei tung I O Beschrei bung DO I O Beschrei bung 750 0515 24 mod_1448445577335_21 docx 196250 1 The I O module contains 1 contact relay per channel The contact rel...

Page 14: ...AC 2 0A Relais 4NO Potential Free Manual Version 1 0 1 The I O module 750 515 can be used with all fieldbus couplers controllers of the WAGO I O SYSTEM 750 Pos 18 2 Dokumentation allgemei n Glieder un...

Page 15: ...196229 1 Figure 1 View Pos 18 5 Serie 750 WAGO I O SYSTEM Ger tebeschrei bung Ansicht Ansicht C ageCl amp _Legende mit LEDs_ohne Leistungskontakte 16 mod_1371816091053_21 docx 124052 1 Table 3 Legend...

Page 16: ...mmen nicht auf Gol dfeder kontakte leg en 7 mod_1266318463636_21 docx 50695 1 Do not place the I O modules on the gold spring contacts Do not place the I O modules on the gold spring contacts in order...

Page 17: ...chl sse 750 0515 24 mod_1448444700681_21 docx 196232 1 Figure 3 CAGE CLAMP Connectors Table 4 Legend for Figure CAGE CLAMP Connectors Channel Designation Connector Function 1 13 1 Relay contact for ex...

Page 18: ...te 750 0515 4DO Agn Bgn Cgn Dgn 24 mod_1448444785751_21 docx 196235 1 Figure 4 Display Elements Table 5 Legend for Figure Display Elements Channel Designation LED State Function 1 Status Relay 1 A OFF...

Page 19: ...ches Schaltbild berschrift 2 4 mod_1240984441312_21 docx 31967 2 1 3 4 Schematic Diagram Pos 18 20 Serie 750 WAGO I O SYSTEM Ger tebeschr eibung Schematische Schaltbilder Digital ausgangskl emmen Sche...

Page 20: ...64 mm Depth 100 mm Weight 56 5 g 3 5 2 Power Supply Table 7 Technical Data Power Supply Current consumption system voltage typ internal 90 mA Current consumption system voltage max internal 95 mA Powe...

Page 21: ...oss section 0 08 mm 2 5 mm AWG 28 14 Stripped lengths 8 mm 9 mm 0 33 in Pos 18 24 3 Serie 750 WAGO I O SYSTEM Ger tebeschr eibung Technische D aten Anschl usstechni k Technische Daten D atenkontakte 1...

Page 22: ...e Manual Version 1 0 1 Pos 18 27 Serie 750 WAGO I O SYSTEM Ger tebeschr eibung Technische D aten Digital ausgangskl emmen Technische D aten 750 0515_Lastgr enz und Lebensdauerkur ve 24 mod_14484450648...

Page 23: ...750 515 4DO 250V AC 2 0A Relais 4NO Potential Free Manual Version 1 0 1 3 5 8 Life Cycle Curve Figure 7 Life Cycle Curve of the Relay Pos 18 28 D okumentati on allgemei n Gli ederungsel emente Seitenw...

Page 24: ...3 mod_1224662755687_0 docx 24460 1 Pos 18 37 Serie 750 WAGO I O SYSTEM Ger tebeschr eibung Zul assung en Ex Zul in Vorbereitung Buskl emme 750 xxxx Ex ohne Variantenang abe Einl eitung 7 mod_12742592...

Page 25: ...Description 25 750 515 4DO 250V AC 2 0A Relais 4NO Potential Free Manual Version 1 0 1 LR Lloyd s Register Env 1 2 3 4 Pos 18 48 D okumentati on allgemei n Gli ederungsel emente Seitenwechsel 3 mod_12...

Page 26: ...stig keit EN 61000 6 2 4 mod_1242797655625_21 docx 33591 1 EMC CE Immunity to interference EN 61000 6 2 Pos 18 52 Alle Serien Allgemeine M odul e Nor men und Richtlini en EM V Nor men Standard EM V C...

Page 27: ...nts in the process image depends on the fieldbus coupler controller used Please take this information from the section Fieldbus Specific Design of the Process Data included in the description concerni...

Page 28: ...ht Vorsicht Verl etzungsgefahr durch scharfkantige M esser kontakte 6 mod_1256193279401_21 docx 43414 1 Risk of injury due to sharp edged blade contacts The blade contacts are sharp edged Handle the I...

Page 29: ...devices Pos 25 8 Serie 750 WAGO I O SYSTEM M ontieren D emontieren Busklemme einf g en 3 mod_1231769726703_21 docx 25989 3 1 5 2 1 Inserting the I O Module 1 Position the I O module so that the tongue...

Page 30: ...4 mod_1239169375203_21 docx 30334 3 1 5 2 2 Removing the I O Module 1 Remove the I O module from the assembly by pulling the release tab Figure 10 Removing the I O Module Example Electrical connectio...

Page 31: ...ent from the power supply 2 Secure the system component against unintentional restart 3 Check if the voltage is positively isolated Pos 29 Serie 750 WAGO I O SYSTEM Anschli e en Leiter an C AGE C LAM...

Page 32: ...TEM 750 750 515 4DO 250V AC 2 0A Relais 4NO Potential Free Manual Version 1 0 1 Figure 11 Connecting a Conductor to a CAGE CLAMP Pos 30 D okumentation allgemei n Glieder ungselemente Seitenwechsel 3 m...

Page 33: ...EM Anschli e en Anschl ussbeispi ele Digitalausgangsklemmen Anschl ussbeispiel e 750 0515_4DO 24 mod_1448444332530_21 docx 196223 22 1 6 3 Protection Class II and III Actuators Figure 12 Connection Ex...

Page 34: ...tly connected to the source of the interference in parallel with the consumer have proved successful in practice Table 14 Protective Circuits for Contacts of Relay Modules Protective Circuits Addition...

Page 35: ...y Defined Induction Voltage Limitation Bipolar Effective Attenuation Advantages and Disadvantages Figure 18 R C Combination medium to short no yes Advantages HF attenuation via power storage suitable...

Page 36: ...er eich Serie 750 3 mod_1234272230203_21 docx 27500 1 The WAGO I O SYSTEM 750 electrical equipment is designed for use in Zone 2 hazardous areas The following sections include both the general identif...

Page 37: ...TEM Einsatz in Ex Ber eichen Kennzeichnung f r Europa gem ATEX und IEC EX berschrift 3 3 mod_1224157620203_21 docx 24185 3 1 7 1 1 Marking for Europe According to ATEX and IEC Ex Pos 36 6 Serie 750 WA...

Page 38: ...pment group Mining M2 Category High level of protection Ex Explosion protection mark d Mb Type of protection and equipment protection level EPL Flameproof enclosure I Explosion group for electrical eq...

Page 39: ...O SYSTEM Einsatz in Ex Ber eichen Beispiel bedruckung der Ex i und IEC Ex i zug elassenen Busklemmen gem C ENELEC und IEC _2013 14 mod_1360569320118_21 docx 111298 1 Figure 21 Side Marking Example for...

Page 40: ...ment protection level EPL protection by enclosure ia Da Type of protection and equipment protection level EPL associated apparatus with intrinsic safety circuits for use in Zone 20 ib Db Type of prote...

Page 41: ...ety device for a category 2 Zone 1 equipment Ex Explosion protection mark nA Gc Type of protection and equipment protection level EPL Non sparking equipment ia Ga Type of protection and equipment prot...

Page 42: ...spi elbedruckung gem NEC 500_2013 14 mod_1360580302684_21 docx 111353 1 Figure 23 Side Marking Example for I O Modules According to NEC 500 Figure 24 Text Detail Marking Example for Approved I O Modul...

Page 43: ...egulations Pos 36 14 Alle Serien Allgemeine M odul e Ei nsatz i n Ex Bereichen Errichtungsbestimmungen Ei nleitung_2013 14 mod_1360582328318_21 docx 111371 1 For the installation and operation of elec...

Page 44: ...n of at least IP 54 according to EN 60529 is achieved 2 Measures have to been taken external to the modules to provide a transient protection that ensures that the rated voltage connected to the power...

Page 45: ...e that ensures a sufficient protection according to EN 60079 0 and EN 60079 1 and the degree of protection IP64 The compliance of these requirements and the correct installation into an enclosure or a...

Page 46: ...ection of at least IP 54 according to IEC 60529 is achieved 2 Measures have to been taken external to the modules to provide a transient protection that ensures that the rated voltage connected to the...

Page 47: ...hat ensures a sufficient protection according to IEC 60079 0 and IEC 60079 1 and the degree of protection IP64 The compliance of these requirements and the correct installation into an enclosure or a...

Page 48: ...s shall contain the following The configuration interface Service connector is for temporary connection only Do not connect or disconnect unless the area is known to be non hazardous Connection or dis...

Page 49: ...Protective Insulation and Class III Safety Extra Low Voltage Actuators 33 Figure 13 Connection Example for Protection Class I Ground Conductor Actuators 33 Figure 14 Diode 34 Figure 15 Zener Diode an...

Page 50: ...Table 7 Technical Data Power Supply 20 Table 8 Technical Data Communication 20 Table 9 Technical Data Outputs 21 Table 10 Technical Data Field Wiring 21 Table 11 Technical Data Data Contacts 21 Table...

Page 51: ...50 515 4DO 250V AC 2 0A Relais 4NO Potential Free Manual Version 1 0 1 Pos 42 D okumentation allgemei n Einband Einband H andbuch Leerseite f r durch 2 teilbar e Seitenzahl Standar ddr uck 3 mod_12192...

Page 52: ...te 2015 9 mod_1285229376516_21 docx 64944 1 WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Intern...

Reviews: