WAGO-I/O-SYSTEM 750
Device Description
21
750-515 4DO 250V AC 2.0A/ Relais 4NO/ Potential Free
Manual
Version 1.0.1
3.5.4
Outputs
Table 9: Technical Data – Outputs
No. of outputs
4 make contacts
Response time
max.
10 ms
Bounce type
typ.
1 ms
Drop-out time
max.
5 ms
Contact Material
AgNi type + Au
Switching operation
(mechanical life)
min.
2 × 10
7
(at 180/Min.)
Switching operation (electrical life)
min.
*)
1 × 10
5
(3 A / 250 VAC, 30 VDC,
resistive load)
5 × 10
4
(5 A / 250 VAC, 30 VDC,
resistive load)
Switching frequency
max.
20/Min (3 A / 250 VAC, 30 VDC)
6/Min (5 A / 250 VAC, 30 VDC)
*)
Please note load limit and life cycle curves!
Pos: 18.24.1 /Alle Serien (Allgemeine M odul e)/Überschriften/Neue Ü berschriften/Ebene 3Anschlusstechni k - Überschrift 3 @ 17\mod_1380123271324_21.docx @ 132788 @ 3 @ 1
3.5.5
Connection Type
Pos: 18.24.2 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Technische D aten/T echnische D aten Verdrahtungsebene CC - 0,08 bis 2,5mm2 @ 17\mod_1380121238809_21.docx @ 132780 @ @ 1
Table 10: Technical Data – Field Wiring
Wire connection
CAGE CLAMP
®
Cross section
0.08 mm² … 2.5 mm², AWG 28 … 14
Stripped lengths
8 mm … 9 mm / 0.33 in
Pos: 18.24.3 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Technische D aten/Anschl usstechni k/Technische Daten D atenkontakte @ 17\mod_1380123495844_21.docx @ 132794 @ @ 1
Table 11: Technical Data – Data Contacts
Data contacts
Slide contact, hard gold plated, self-
cleaning
Pos: 18.25 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Technische D aten/Klimatische U mgebungsbeding ungen/T echnische D aten Kli mat. U mgebungsbed. ohne erw. T emp. 0...55°C/- 25...+ 85°C @ 5\mod_1247657968368_21.docx @ 37603 @ 3 @ 1
3.5.6
Climatic Environmental Conditions
Table 12: Technical Data – Climatic Environmental Conditions
Operating temperature range
0 °C … 55 °C
Storage temperature range
−
25 °C … +85 °C
Relative humidity without condensation Max. 95 %
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75 %
SO
2
≤
25 ppm
H
2
S
≤
10 ppm
Special conditions
Ensure that additional measures for
components are taken, which are used in
an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
Pos: 18.26 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1