WAGO-I/O-SYSTEM 750 XTR
Commissioning
73
750-486/040-000 4AI 0/4-20mA NE43 Ex i XTR
Manual
Version 1.0.0
Table 41:
Calibration
Menu Item
Option
Description
Selection
of the cali-
bration
method
Activate factory configuration
Activate
factory
calibration.
*)
Factory calibration is activated and user
calibration is deactivated.
Factory calibration is deactivated and user
calibration is activated.
Gain
The Gain value is specified by the
manufacturer.
Offset The Offset value is specified by the
manufacturer.
Activate user calibration
Activate user
calibration
User calibration is activated and factory
calibration is deactivated.
You determine the gain and offset value
yourself.
*)
User calibration is deactivated and factory
calibration is activated.
Gain
Enter the Gain value for the user calibration.
The Gain value changes the gain factor of the
A/D raw value.
The value entered must fall within the value
range 0 … 65535.
The resolution is 1/8192.
Offset
Enter the Offset value for the user calibration.
The Offset value moves the zero point of the
A/D raw value (offset on the y axis).
The value entered must fall within the value
range −32768 … 32767.
A/D raw value
Raw value of the analog/digital converter. This is a 14-
bit value.
If the channel is deactivated, “N/A” (not available) is
displayed.
The A/D raw value is read cyclically from the I/O
module.
Current [mA]
Display of the calibrated input current in milliamps
(mA).
This is a 32-bit value.
If the channel is deactivated, “N/A” (not available) is
displayed.
The input current value is read cyclically from the I/O
module.
*)
Factory setting