WAGO I/O System 750 XTR
Commissioning 65
750-471/040-000 4AI U/I Diff Galv XTR
Manual
Version 1.0.2
7.1.4.2 Channel Settings
Figure 19: Parameter „Channel“
In the menus
Channel 1 … 4
you can make channel granular settings:
Table 41: Parameter „Channel“
Selection Field
Possible Settings
Signal type
The measurement range can be set and the channel
switched on or off here.
Channel
deactivated
The channel is switched off. 0x7FFF is
delivered as process value.
0 … 10 V
± 10 V
± 200 mV
0 … 20 mA
4 … 20 mA*
3,6 … 21,0 mA (Namur NE 43)
± 20 mA
Input filter
Whether the input filter frequency set for this channel in
the “General” menu should be suppressed can be set
with this parameter.
Off*
Input filter is OFF.
On
Input filter is ON.
Channel Diagnosis
The diagnostics for one channel can be switched on or
off here.
Off
Channel diagnostics is OFF.
On*
Channel diagnostics is ON.
Diagnosis: Overload
The overload diagnostics can be switched on or off
here.
On
Overload diagnostics is OFF.
Off*
Overload diagnostics is ON.
Diagnosis: Wire break
The wire break diagnostics for one channel can be
switched on or off here.
On
Wire break diagnostics is ON.