52 Process Image
WAGO I/O System 750 XTR
750-471/040-000 4AI U/I Diff Galv XTR
Manual
Version 1.0.2
Table 37: Signal Type “Namur NE43”, Amount/sign format with Status Information in the Process
Image
Measuring range [mA]
Process value
Statusbyte
hex.
Error
LED
Namur NE43
Binary
Hex.
Dec.
XFÜ
1)
<
−
14,0 mA
1000.0001.1000.1
011 0x818B
−
397
0x50
on
Neg. sensor overload
3)
< 1,0
1000.0001.1000.1
011 0x818B
−
397
0x60
on
Wire break or
Overload
3)
< 3,6
1000.0001.1000.1
011 0x818B
−
397
0x41
on
Underrange
2)
3,8
1000.0001.1000.1
000 0x8188
−
400
0x00
off
4,0
0000.0000.0000.0
000 0x0000
0
0x00
off
5,6
0000.1100.0110.1
000 0x0C68 3176
0x00
off
7,2
0001.1000.1100.1
000 0x18C8 6344
0x00
off
8,8
0010.0101.0011.1
000 0x2538 9528
0x00
off
10,4
0011.0001.1010.0
000 0x31A0 12704
0x00
off
12,0
0011.1110.0000.1
000 0x3E08 15880
0x00
off
13,6
0100.1010.0111.1
000 0x4A78 19064
0x00
off
15,2
0101.0110.1110.0
000 0x56E0 22240
0x00
off
16,8
0110.0011.0100.1
000 0x6348 25416
0x00
off
18,4
0110.1111.1011.0
000 0x6FB0 28592
0x00
off
20,0
0111.1100.0001.1
000 0x7C18 31768
0x00
off
20,5
0111.1111.1111.1
000 0x7FF8 32760
0x00
off
Exceeding
2)
0111.1111.1111.1
011 0x7FFB 32763
0x42
on
> 21,0
Sensor overload
3)
0111.1111.1111.1
011 0x7FFB 32763
0x50
on
> 22,0
1)
Status bits: X: not used, F= error, Ü= overrange
2)
When underrange / overrange limit is ON
3)
When wire break / overload diagnostics is ON