WAGO I/O System 750 XTR
Process Image 43
750-471/040-000 4AI U/I Diff Galv XTR
Manual
Version 1.0.2
4.3
Process Data
4.3.1
Overview of Sensor Types
The following table serves as an overview of all supported sensor types. The
following sections provide detailed information about the individual sensor types.
The signal types “0 to 10 V,” “0 to 20 mA,” “4 to 20 mA” and types “±10 V,”
“±200 mV,” “±20 mA” are summarized in table form. Furthermore, a distinction is
made between whether or not the I/O module is configured with or without status
information.
Table 27: Process Data, Signal Types
Bits 0 … 3 of
register 32
Signal type
Measuring range
Measuring value
resolution
0x00
Channel is not activ
0x01
0 … 10 V
0 … +10 V
15 Bit
0x02
±10 V
−10
… +10 V
16 Bit
0x03
0 … 20 mA
0 … + 20mA
15 Bit
0x04
4 … 20 mA
+4 … +20 mA
15 Bit
0x05
3.6 … 21 mA
+3.8 … +20.5 mA
15 Bit
0x06
±20 mA
+20 …
−
20 mA
16 Bit
0x07
±200 mV
−200 …+
200 mV
16 Bit
Observe the Information about Process Resolution
The specification of the process value resolution (see table on previous page)
refers to measured values within the limits set for the measurement range.
Over- and underranges refer to these measurement range limits!