WAGO I/O System 750 XTR
Commissioning 71
750-471/040-000 4AI U/I Diff Galv XTR
Manual
Version 1.0.2
The I/O module can also be parameterized via PROFIBUS and PROFINET
device description (GSD file).
7.2
Configuration and Parameterization via GSD File
Behavior after Overwriting with WAGO-I/O-
CHECK
!
If WAGO-I/O-
CHECK
is used to overwrite a parameterization made with the GSD
file, the I/O module operates with the WAGO-I/O-
CHECK
settings until the
750-333/040-000 Fieldbus Couplers are restarted.
After restart, the I/O module is re-parameterized via PROFIBUS using the GSD
settings.
7.2.1
4AI U/I Diff/Galv Configuration
7.2.1.1 PROFIBUS DP Fieldbus Couplers 750-333/040-000
When using the aforementioned PROFIBUS DP fieldbus devices, the process
image size is configured by selecting the corresponding GSD entry.
Table 44: PROFIBUS DP Configuration
GSD Entry
PI-Length/[Byte]
Data Type
Inst.
Module
Sub-
Module
I
O
75x-471 4AI/U/I Diff/Galv
n/a
8
n/a
INT16
4
75x-471 4AI/U/I Diff/Galv RA
12
12
{UINT8, INT16}