2787-2154
Configuration
44
Product manual | Version: 1.0.2
Power Supply Pro 2
Section
Parameters
Description
Hiccup mode
If this checkbox is selected, the “Hiccup Mode” over-
load behavior is enabled. You can find more informa-
tion in section
8
Electronic circuit breaker
If this checkbox is selected, the “Electronic Circuit
Breaker” overload behavior is enabled. In the event of
overload, the power supply works like an electronic cir-
cuit breaker and switches the energy off with a time
delay. You can find more information in section
8
“Electronic Circuit Breaker” Mode [
Trip current
Here you can enter the trip current (unit: mA) for the
“Electronic Circuit Breaker” overload behavior.
Trip delay
Here you can enter the trip delay (unit: ms) for the
“Electronic Circuit Breaker” overload behavior.
Latching after thermal over-
load
If this checkbox is selected, the “Latching Shutdown on
Thermal Overload” overload behavior is enabled. After
an overtemperature event, the power supply no longer
automatically switches the output back on as soon as it
has cooled off. To switch the output back on, manual
intervention is necessary. The following options are
available for this:
•
Communication interface
•
Buttons
•
Digital input
You can find more information in section
8
Shutdown on Thermal Overload” Mode [
PowerBoost
If this checkbox is selected, the “Power Boost” over-
load behavior is enabled. The power supply offers up
to 150 % of the output power for 5 s. You can find
more information in section
8
TopBoost
If this checkbox is selected, the “Top Boost” overload
behavior is enabled. The power supply provides up to
600 % more output power for 15 s. You can find more
information in section
8
.