Figure 4 Standard dual tank system controlled by SUNGO SL.

5.2 Standard Dual Tank System

P3

P2

BWM

T1

T2

T3

Ttw

P1

A1

T1

SECUSOL

Ta

T7

T5

T1

T3 T2

Heating circuit

Hot water

Cold water

Measuring the yield

Solar
return-flow

Collector field (EURO C22)

Oil or gas
boiler

T1:

Collector sensor

T2:

Tank sensor, bottom

T3:

Tank 1 sensor, top (optional)

T5:

Yield measurement, return flow sensor

T7:

Yield measurement, volume flow metre

P1:

Solar circuit pump

P2:

Heating circuit pump

P3:

Tank charging pump

Ttw:

Hot water sensor (heating control)

BWM: Thermostatic mixing valve

Collector field

5.3 SECUSOL System

P1

P3

P2

P1

CIRCO

Vu

T3 T2

T1

T4

A1

A2

M

ECOplus

T1

T5

T7

AB

A

B

T4

T2

T1

T3

Ttw

Collector field

Heating circuit

Oil or gas
boiler

Hot water

Cold water

Solar
return-flow

Collector field

Measuring the yield

P1: Solar circuit pump
P2: Heating circuit pump
P3: Tank charging pump
Vu: Switch-over valve, tank charging

T1: Collector sensor
T2: Tank 1 sensor, bottom
T3: Tank 1 sensor, top
T4: Tank 2 sensor, bottom
T5: Yield measurement, return flow sensor
T7: Yield measurement, volume flow metre

Figure 5 SECUSOL system controlled by SUNGO SL.

Subject to modifications, errors excepted. · © Wagner & Co, 2008 · www.wagner-solar.com

12

WAGNER & CO · Zimmermannstraße 12 · D-35091 Cölbe/Marburg ·

+49 6421 80 07-0 · Fax 80 07-22

Summary of Contents for SUNGO SL

Page 1: ...emperature in crease Balance reset values 5 temperature inputs PT1000 1 output speed controlled The sensor T5 solar return and an external volume measuring device provide energy measurements in kWh NEW now also SECUSOL system ready Contents 1 TechnicalDescription 2 2 GeneralSafety Guidelines 4 2 1 Installer s Qualifications 4 2 2 OperatingRequirements 4 2 3 InstallationandOperatingInformation 4 3 ...

Page 2: ...T2 tank bottom the display also shows balance val ues which represent the smallest and biggest temperature values for each sensor After reset the actual temperature value is displayed Manual Operation Allows switching inputs and outputs on or off manually On exiting the manual operation menu the software returns to automatic operation The manual operation menu can be used foramaximumof 8hours Afte...

Page 3: ...A2 for switching between tanks with the help of a 3 way valve Change the menu item 0 1 to 0 2 in order to control a dual tank system Note If the dual tank option is selected menu item 10 can no longer be activated Preference The SUNGO SL always uses tank 1 as a preference for the dual tank option This cannot be changed Thermostat The thermostat function for switching on can be set at a range betwe...

Page 4: ...llation and Operating Information Any installation and wiring work has to be carried out in an idle state as during operation the voltage on the out side of the triacs is 230 V Mains power must be connected to the control from out side the solar station via an external ON OFF Switch This is also required to activate the special functions menu through switching the mains power ON OFF Operating temp...

Page 5: ...h a pro tective plug to a socket The control is suitable for mains operation at approx 230 V 50 Hz All earth wires are connected to the PE terminals The neutral terminals N are connected electrically Switching output A1 is a 230 V normally open contact which is activated via speed control Switching output A2 is purely a normally open contact Connecting the temperature sensors The wires of the temp...

Page 6: ... Tank temp top thermostat additional sensor Temperature thermostat return flow boost sink Time slot thermostat Tank temp mid section return flow boost source Confirm and save symbol System error Settings menu Information menu Temperature difference Numerical display for temp or sensor errors Collector temperature Symbol for reset value Tank temp bottom Pump ON Pump OFF Output A1 Output A2 ...

Page 7: ...ching on diff T3 T4 return temperature increase Min temp level return temperature increase Temp limitation return temperature increase Stop time window 3 thermostat Start time window 3 thermostat Stop time window 2 thermostat Start time window 2 xx thermostat Stop time window 1 thermostat Start time window 1 thermostat Temperature limitation tank bottom Switching on difference T1 T2 solar Switchin...

Page 8: ...2 total if 2 tank system is selected Balance h R operating hours tank 1 or 2 since last reset if 2 tank system is selected Balance display resettable h Thermostat or return temperature increase drain Current value C Heat counter return flow value corresponds to collector temperature Current value C Heat counter total yield Balance kWh R heat counter since last reset Balance display resettable kWh ...

Page 9: ...ng off difference thermostat 1 1 40 K 5 K Additional sensor difference for tank top can be selected in heating function 1 3 20 K 10 K Start time slot 1 thermostat 1 0 00 23 59 0 00 Stop time slot 1 thermostat 1 0 00 23 59 23 59 Start time slot 2 thermostat 1 0 00 23 59 0 00 Stop time slot 2 thermostat 1 0 00 23 59 0 00 Start time slot 3 thermostat 1 0 00 23 59 0 00 Stop time slot 3 thermostat 1 0 ...

Page 10: ... C 135 C 3 Collector Cooling Off 0 On 1 Activation of collector cooling Cannot be activated with SECUSOL 0 or 1 1 4 Collector cooling start temperature 100 150 C 110 C 5 Storage tank Cooling Off 0 On 1 Activation of tank cooling Only possible with collector cooling Cannot be activated with SECUSOL 0 or 1 0 6 Switching off temperature 30 90 C 60 C 7 Measuring the Yield Off 0 On 1 Activation of yiel...

Page 11: ...ring replace sensors if required 4 7 Service Sensor Control Resistance values for Pt1000 sensors in relation to the temperature 10 C 0 C 10 C 20 C 30 C 40 C 50 C 60 C 70 C 80 C 90 C 100 C 110 C 961 Ω 1000 Ω 1039 Ω 1078 Ω 1117 Ω 1155 Ω 1194 Ω 1232 Ω 1271 Ω 1309 Ω 1347 Ω 1385 Ω 1423 Ω The working condition of the sensor can be checked with this table and an Ohm meter 5 Application examples 5 1 Stand...

Page 12: ...ic mixing valve Collector field 5 3 SECUSOL System P1 P3 P2 P1 CIRCO Vu T3 T2 T1 T4 A1 A2 M ECOplus T1 T5 T7 AB A B T4 T2 T1 T3 Ttw Collector field Heating circuit Oil or gas boiler Hot water Cold water Solar return flow Collector field Measuring the yield P1 Solar circuit pump P2 Heating circuit pump P3 Tank charging pump Vu Switch over valve tank charging T1 Collector sensor T2 Tank 1 sensor bot...

Reviews: