4.4 Manual Operation Menu

Manual operation menu

Menu item

Description

Range

Default setting

Off = 0/On = 1

Switching the solar circuit pump on or off manually (A1)

0 – 1

0

Off = 0/On = 1

Switching output A2 on or off manually (RLA or thermostat)

0 – 1

0

Activation of manual operation lag time in automatic mode

0 – 600 min

0 min

4.5 Special Functions Menu

During the first minute after switching on the control

activate the special functions menu by selecting it so that parameters can be altered. The menu stays active for 1 minute af-
ter exiting it.
On exiting the menu the parameters can only be viewed but not changed again. Place the control in the idle position once
again if you need to alter any functions.

Special functions menu

Menu
item

Application

Description

Range

Default
setting

0

System choice

0 – 1: Standard single tank system
0 – 2: Standard dual tank system
0 – 3: SECUSOL system (see SECUSOL instructions for further info)

1 – 3

1

1

System
Protection

Off = 0/On = 1

Activation of system protection.
Cannot be activated with SECUSOL!

0 or 1

1

2

System protection start temperature

115 – 200 °C

135 °C

3

Collector
Cooling

Off = 0/On = 1

Activation of collector cooling.
Cannot be activated with SECUSOL!

0 or 1

1

4

Collector cooling start temperature

100 – 150 °C

110 °C

5

Storage tank
Cooling

Off = 0/On = 1

Activation of tank cooling. Only possible with collector cooling.
Cannot be activated with SECUSOL!

0 or 1

0

6

Switching off temperature

30 – 90 °C

60 °C

7

Measuring the
Yield

Off = 0/On = 1

Activation of yield measurement

0 or 1

0

8

Frost protection type
8-1: DC20 for standard systems
8-2: DC40 for vacuum tube collectors (ready mix)

1 or 2

1

9

Glycol fraction in %.
0 %

= No Glycol (pure water)

100 % = Pure Glycol (no water)
Note: Glycol fraction for solar circuit can only be selected with DC20!

0 – 100 %

40 %

10

Function
selection

10 – 0: Additional functions off
10 – 1: Thermostat, heating
10 – 2: Thermostat, heating with additional sensor T3 (tank, top)
10 – 3: Thermostat, cooling
10 – 4: return temperature increase

0 – 4

0

11

Vacuum Tube
collector function

Off = 0/On = 1

Activation of vacuum tube collector function

0 or 1

0

12

Run time of solar circuit pump from reaching the switching on value

1 – 60 s

15 s

13

Switching on value for temperature increase at sensor T1 (collector)

1.0 – 5.0 K

1.0 K

The special functions menus should only be edited by expert personnel. Incorrect settings may adversely affect the solar heating system.

T stop

__

Summary of Contents for SUNGO SL

Page 1: ...emperature in crease Balance reset values 5 temperature inputs PT1000 1 output speed controlled The sensor T5 solar return and an external volume measuring device provide energy measurements in kWh NEW now also SECUSOL system ready Contents 1 TechnicalDescription 2 2 GeneralSafety Guidelines 4 2 1 Installer s Qualifications 4 2 2 OperatingRequirements 4 2 3 InstallationandOperatingInformation 4 3 ...

Page 2: ...T2 tank bottom the display also shows balance val ues which represent the smallest and biggest temperature values for each sensor After reset the actual temperature value is displayed Manual Operation Allows switching inputs and outputs on or off manually On exiting the manual operation menu the software returns to automatic operation The manual operation menu can be used foramaximumof 8hours Afte...

Page 3: ...A2 for switching between tanks with the help of a 3 way valve Change the menu item 0 1 to 0 2 in order to control a dual tank system Note If the dual tank option is selected menu item 10 can no longer be activated Preference The SUNGO SL always uses tank 1 as a preference for the dual tank option This cannot be changed Thermostat The thermostat function for switching on can be set at a range betwe...

Page 4: ...llation and Operating Information Any installation and wiring work has to be carried out in an idle state as during operation the voltage on the out side of the triacs is 230 V Mains power must be connected to the control from out side the solar station via an external ON OFF Switch This is also required to activate the special functions menu through switching the mains power ON OFF Operating temp...

Page 5: ...h a pro tective plug to a socket The control is suitable for mains operation at approx 230 V 50 Hz All earth wires are connected to the PE terminals The neutral terminals N are connected electrically Switching output A1 is a 230 V normally open contact which is activated via speed control Switching output A2 is purely a normally open contact Connecting the temperature sensors The wires of the temp...

Page 6: ... Tank temp top thermostat additional sensor Temperature thermostat return flow boost sink Time slot thermostat Tank temp mid section return flow boost source Confirm and save symbol System error Settings menu Information menu Temperature difference Numerical display for temp or sensor errors Collector temperature Symbol for reset value Tank temp bottom Pump ON Pump OFF Output A1 Output A2 ...

Page 7: ...ching on diff T3 T4 return temperature increase Min temp level return temperature increase Temp limitation return temperature increase Stop time window 3 thermostat Start time window 3 thermostat Stop time window 2 thermostat Start time window 2 xx thermostat Stop time window 1 thermostat Start time window 1 thermostat Temperature limitation tank bottom Switching on difference T1 T2 solar Switchin...

Page 8: ...2 total if 2 tank system is selected Balance h R operating hours tank 1 or 2 since last reset if 2 tank system is selected Balance display resettable h Thermostat or return temperature increase drain Current value C Heat counter return flow value corresponds to collector temperature Current value C Heat counter total yield Balance kWh R heat counter since last reset Balance display resettable kWh ...

Page 9: ...ng off difference thermostat 1 1 40 K 5 K Additional sensor difference for tank top can be selected in heating function 1 3 20 K 10 K Start time slot 1 thermostat 1 0 00 23 59 0 00 Stop time slot 1 thermostat 1 0 00 23 59 23 59 Start time slot 2 thermostat 1 0 00 23 59 0 00 Stop time slot 2 thermostat 1 0 00 23 59 0 00 Start time slot 3 thermostat 1 0 00 23 59 0 00 Stop time slot 3 thermostat 1 0 ...

Page 10: ... C 135 C 3 Collector Cooling Off 0 On 1 Activation of collector cooling Cannot be activated with SECUSOL 0 or 1 1 4 Collector cooling start temperature 100 150 C 110 C 5 Storage tank Cooling Off 0 On 1 Activation of tank cooling Only possible with collector cooling Cannot be activated with SECUSOL 0 or 1 0 6 Switching off temperature 30 90 C 60 C 7 Measuring the Yield Off 0 On 1 Activation of yiel...

Page 11: ...ring replace sensors if required 4 7 Service Sensor Control Resistance values for Pt1000 sensors in relation to the temperature 10 C 0 C 10 C 20 C 30 C 40 C 50 C 60 C 70 C 80 C 90 C 100 C 110 C 961 Ω 1000 Ω 1039 Ω 1078 Ω 1117 Ω 1155 Ω 1194 Ω 1232 Ω 1271 Ω 1309 Ω 1347 Ω 1385 Ω 1423 Ω The working condition of the sensor can be checked with this table and an Ohm meter 5 Application examples 5 1 Stand...

Page 12: ...ic mixing valve Collector field 5 3 SECUSOL System P1 P3 P2 P1 CIRCO Vu T3 T2 T1 T4 A1 A2 M ECOplus T1 T5 T7 AB A B T4 T2 T1 T3 Ttw Collector field Heating circuit Oil or gas boiler Hot water Cold water Solar return flow Collector field Measuring the yield P1 Solar circuit pump P2 Heating circuit pump P3 Tank charging pump Vu Switch over valve tank charging T1 Collector sensor T2 Tank 1 sensor bot...

Reviews: