4.6 Service – System Messages

System information with display

Display

Description

Remedy

System messages

All system messages are displayed with a blinking caution symbol. In case of sensor errors the sensor in
question is also marked with short circuit or interruption symbol.

Interruption

The sensor on the display or the pipe is
interrupted.

Test the resistance value of the sensors and compare with
the tables.

Check all connections to the sensor.

Short circuit

There is a short circuit on the sensor on the
display, the cable or the output on the
control.

dT too high

A value of 20 K is added to the switch-on
difference between T1 and T2. The message
is displayed if after 30 minutes the total
difference has not been reduced.

Check wiring to the pump

Check system for air and vent if required

Check sensors and sensor wiring, replace sensors if
required

4.7 Service – Sensor Control

Resistance values for Pt1000 sensors in relation to the temperature

-10 °C

0 °C

10 °C

20 °C

30 °C

40 °C

50 °C

60 °C

70 °C

80 °C

90 °C

100 °C

110 °C

961

1000

1039

1078

1117

1155

1194

1232

1271

1309

1347

1385

1423

The working condition of the sensor can be checked with this table and an Ohm meter.

5. Application examples

5.1 Standard Single Tank System

!

Blinking

!

Blinking

!

Blinking

° C

!

Blinking

° C

Ttw

T4

T1

T3

T2

A

AB

B

Vr

P2

P3

TE

RMO

P1

P1

CIRCO

T4

A1

T1

A2

T2

T3

T7

T5

T1

Measuring the yield

Solar
return-flow

Collector field

Cold water

Hot water

Version 1 – TERMO Combi Cylinder

Heating circuit

Oil or gas
boiler

P1: Solar circuit pump
P2: Heating circuit pump
P3: Tank charging pump
Vr: Switch-over valve for return temperature increase

T1: Collector sensor
T2: Tank sensor, bottom
T3: Tank sensor, middle
T4: Sensor heating return-flow
T5: Yield measurement, return flow sensor
T7: Yield measurement, volume flow metre

Collector field

Figure 3 Standard single tank system controlled by SUNGO SL.

Summary of Contents for SUNGO SL

Page 1: ...emperature in crease Balance reset values 5 temperature inputs PT1000 1 output speed controlled The sensor T5 solar return and an external volume measuring device provide energy measurements in kWh NEW now also SECUSOL system ready Contents 1 TechnicalDescription 2 2 GeneralSafety Guidelines 4 2 1 Installer s Qualifications 4 2 2 OperatingRequirements 4 2 3 InstallationandOperatingInformation 4 3 ...

Page 2: ...T2 tank bottom the display also shows balance val ues which represent the smallest and biggest temperature values for each sensor After reset the actual temperature value is displayed Manual Operation Allows switching inputs and outputs on or off manually On exiting the manual operation menu the software returns to automatic operation The manual operation menu can be used foramaximumof 8hours Afte...

Page 3: ...A2 for switching between tanks with the help of a 3 way valve Change the menu item 0 1 to 0 2 in order to control a dual tank system Note If the dual tank option is selected menu item 10 can no longer be activated Preference The SUNGO SL always uses tank 1 as a preference for the dual tank option This cannot be changed Thermostat The thermostat function for switching on can be set at a range betwe...

Page 4: ...llation and Operating Information Any installation and wiring work has to be carried out in an idle state as during operation the voltage on the out side of the triacs is 230 V Mains power must be connected to the control from out side the solar station via an external ON OFF Switch This is also required to activate the special functions menu through switching the mains power ON OFF Operating temp...

Page 5: ...h a pro tective plug to a socket The control is suitable for mains operation at approx 230 V 50 Hz All earth wires are connected to the PE terminals The neutral terminals N are connected electrically Switching output A1 is a 230 V normally open contact which is activated via speed control Switching output A2 is purely a normally open contact Connecting the temperature sensors The wires of the temp...

Page 6: ... Tank temp top thermostat additional sensor Temperature thermostat return flow boost sink Time slot thermostat Tank temp mid section return flow boost source Confirm and save symbol System error Settings menu Information menu Temperature difference Numerical display for temp or sensor errors Collector temperature Symbol for reset value Tank temp bottom Pump ON Pump OFF Output A1 Output A2 ...

Page 7: ...ching on diff T3 T4 return temperature increase Min temp level return temperature increase Temp limitation return temperature increase Stop time window 3 thermostat Start time window 3 thermostat Stop time window 2 thermostat Start time window 2 xx thermostat Stop time window 1 thermostat Start time window 1 thermostat Temperature limitation tank bottom Switching on difference T1 T2 solar Switchin...

Page 8: ...2 total if 2 tank system is selected Balance h R operating hours tank 1 or 2 since last reset if 2 tank system is selected Balance display resettable h Thermostat or return temperature increase drain Current value C Heat counter return flow value corresponds to collector temperature Current value C Heat counter total yield Balance kWh R heat counter since last reset Balance display resettable kWh ...

Page 9: ...ng off difference thermostat 1 1 40 K 5 K Additional sensor difference for tank top can be selected in heating function 1 3 20 K 10 K Start time slot 1 thermostat 1 0 00 23 59 0 00 Stop time slot 1 thermostat 1 0 00 23 59 23 59 Start time slot 2 thermostat 1 0 00 23 59 0 00 Stop time slot 2 thermostat 1 0 00 23 59 0 00 Start time slot 3 thermostat 1 0 00 23 59 0 00 Stop time slot 3 thermostat 1 0 ...

Page 10: ... C 135 C 3 Collector Cooling Off 0 On 1 Activation of collector cooling Cannot be activated with SECUSOL 0 or 1 1 4 Collector cooling start temperature 100 150 C 110 C 5 Storage tank Cooling Off 0 On 1 Activation of tank cooling Only possible with collector cooling Cannot be activated with SECUSOL 0 or 1 0 6 Switching off temperature 30 90 C 60 C 7 Measuring the Yield Off 0 On 1 Activation of yiel...

Page 11: ...ring replace sensors if required 4 7 Service Sensor Control Resistance values for Pt1000 sensors in relation to the temperature 10 C 0 C 10 C 20 C 30 C 40 C 50 C 60 C 70 C 80 C 90 C 100 C 110 C 961 Ω 1000 Ω 1039 Ω 1078 Ω 1117 Ω 1155 Ω 1194 Ω 1232 Ω 1271 Ω 1309 Ω 1347 Ω 1385 Ω 1423 Ω The working condition of the sensor can be checked with this table and an Ohm meter 5 Application examples 5 1 Stand...

Page 12: ...ic mixing valve Collector field 5 3 SECUSOL System P1 P3 P2 P1 CIRCO Vu T3 T2 T1 T4 A1 A2 M ECOplus T1 T5 T7 AB A B T4 T2 T1 T3 Ttw Collector field Heating circuit Oil or gas boiler Hot water Cold water Solar return flow Collector field Measuring the yield P1 Solar circuit pump P2 Heating circuit pump P3 Tank charging pump Vu Switch over valve tank charging T1 Collector sensor T2 Tank 1 sensor bot...