CT 36-400E
Operation
19
2.6
Extension Cords
When choosing an extension cord, make sure it has adequate wire
size for safety. An undersized cord will cause a drop in line voltage
resulting in a loss of power and overheating. The table below shows
the correct wire size to use depending on cord length. If in doubt, use
the next heavier cord size. On motors being used outdoors, use
extension cords rated for outdoor use.
Improper use of extension cords can cause overheating and create
serious fire or shock hazards. NEVER use worn or damaged cords!
Extension cord length
(meters)
Minimum extension cord size
(mm
2
)
400 V / 3Ø / 7.3 Amp
0–20
1.0
20–40
1.5
40–80
1.5
80–100
2.5
WARNING