UR3274U - User manual
31
1012
Manual reset:
write 0 to reset all the alarms.
In reading
(0=not resettable, 1=resettable):
Bit0 = Alarm 1
Bit1 = Alarm 2
WO
0
1013
Error flags
Bit0 = Eeprom writing error
Bit1 = Eeprom reading error
Bit2 = Cold junction error
Bit3 = Process error (sensor)
Bit4 = Generic error
Bit5 = Hardware error
Bit6 = Master off-line
Bit7 = Missing calibration data
RO
0
1014
Cold junction temperature
(tenths of degree)
RO
-
1015
Start/Stop
0=controller in STOP
1=controller in START
R/W
0
1016
Lock conversion ON/OFF
0=Lock conversion off
1=Lock conversion on
R/W
0
1017
Tuning ON/OFF
0=Tuning off
1=Tuning on
R/W
0
1018
Automatic/manual selection
0=automatic
1=manual
R/W
0
1019
OFF LINE
*
time (milliseconds)
R/W
0
1100
Process visualized (decimal as
display)
RO
-