40
UR3274U - User manual
9
o.caL.
Offset Calibration
number added to process value visualized on display
(usually correcting the ambient temperature value).
-999…+1000
[digit
3
] for linear sensors and potentiometers.
-99.9…+100.0
(degrees.tenths for temperature sensors). >
Default
: 0.0.
10
G.caL.
Gain Calibration
this % is multiplied with displayed value to calibrate the
process value.
-99.9%…+100.0
% >
Default
: 0.0
11
act.t.
Action type
regulation type
heat
Heating (N.A.) >
Default
cooL,
Cooling (N.C.)
H.o.o.s.
If process is above setpoint, output is disabled
(Heating).
12
c. re.
Command Reset
type of reset for state of command contact (always
automatic in PID functioning).
a.re.
Automatic Reset >
Default
m.re.
Manual Reset
m.re.s.
Manual Reset Stored
13
c. s.e.
Command State Error
state of contact for command output in case of error.
c.o.
>
Default
c.c.
14
c. Ld.
Command Led
state of OUT1 led corresponding to the relevant contact.
c.o.
c.c.
>
Default