UR3274U - User manual
19
Press
Effect
Do
1
FNC
for 3 sec.
Display 1 shows
0000
with the 1st digit
flashing, while display
2 shows
pass
2
or
Change the flashing
digit and move to the
next one using the
SET
key.
Enter password
9999
3
SET
to confirm
Instrument loads
default settings
Turn off and restart
the instrument
7.10
LATCH ON Functions
For use with input
Pot.1
(potentiometer 6KΩ) and
Pot.2
(po-
tentiometer 150KΩ) and with linear input (0…10V, 0...40mV,
0/4…20mA), it is possible to associate start value of the scale
(parameter 6
Lo.L.i.
) to the minimum position of the sensor
and value of the scale end (parameter 7
up.L.i.
) to the maxi-
mum position of the sensor (parameter 8
Latc.
configured as
std.
).
It is also possible to fix the point in which the controller will
display 0 (however keeping the scale range between
Lo.L.i.
and
up.L.i.
) using the “virtual zero” option by setting
u.0st.
or
u.0in.
in parameter 8
Latc.
If you set
u.0in.
the virtual zero
will reset after each activation of the tool; if you set
u.0st.
the
virtual zero remains fixed once tuned.
To use the LATCH ON function, configure according to requi-
red operation the parameter
Latc.
2
2
The tuning procedure starts by exiting the configuration after changing