W.E. Anderson 185 Series Installation And Operating Instructions Manual Download Page 3

6. Insert the connection bar attached on the actuator clamp into the slot of Series
185’s feedback lever. In order to reduce hysteresis, it should appear as shown:

7. Check that the Series 185’s feedback lever is level at 50% of valve stroke. If
not, move bracket or feedback link until it is level. Product linearity becomes work
if Series 185 is installed without being level at 50% of valve stroke.

8. Check valve stroke. The numbers indicating stroke are carved in the Series
185’s feedback lever. Set the connection bar attached on the actuator clamp to
the number on the feedback lever applicable to valve stroke as shown in the
following picture. To set the connection bar and the number, move the bracket
attached on Series 185 or connection bar from side to side. 

NOTE: After installation, operate the valve from 0 to 100% stroke using an air
filter regulator on the actuator. When the stroke is both 0 and 100%, the feedback
lever should not reach to the lever stopper on the backside of the Series 185 unit.
If the feedback lever reaches the lever stopper, move attachment of Series 185
away from the yoke center. 

9. Once the Series 185 is installed according to the above procedures, tighten the
bolts and nuts of the bracket and feedback lever connection bar completely. 

Series 285 Installation

Series 285 is designed for rotary motion valves such as Dwyer Instruments’ ball
and butterfly valves using rack and pinion, scotch yoke or complex type actuators
whose stem is rotated 90°. Series 285 positioners consist of the following
components:
Series 285 main body
Fork lever and lever spring to attach on actuator 
1 bracket
Four hex bolts M8x1.25P
Four M8 plate washers

Series 285 Installation Example of Fork Lever

60

50

40

90

°

50%

LCD SCREEN

SMART POSITIONER

30

10

20

40

50

60

70

150

140

130

120

110

100

90

80

40

20

10

30

80

90

100

110 120 130

140 150

70

60

50

No

 To

uc

h !

Stroke 40 mm

Stroke 90 mm

Summary of Contents for 185 Series

Page 1: ...essure during operation Simple to use auto calibration Easily equipped on small actuators because of its small size Low air consumption reduces operating cost Can be used in low voltage 8 5 V leaving...

Page 2: ...5 Four M8 plate washers Installing Series 185 with Bracket It is necessary to make a proper bracket to attach on the actuator yoke The most important considerations in the design of the bracket are as...

Page 3: ...gulator on the actuator When the stroke is both 0 and 100 the feedback lever should not reach to the lever stopper on the backside of the Series 185 unit If the feedback lever reaches the lever stoppe...

Page 4: ...o NAMUR shaft 5 Once the fork lever position is set lock the check nuts on the bottom of the fork lever by turning clockwise Set the upper height of the fork lever to 24 to 43 6 to 11 mm lower than th...

Page 5: ...the positioner and system 2 The ground terminals are inside the terminal in the center of the terminal plate and outside terminal beside outer cable entry Use any ground terminal that is available and...

Page 6: ...by users in the field after being supplied the positioner unit whose parameters were set by the valve company 1 Push ENTER for 6 seconds in RUN mode and AUTO CAL message should appear 2 Push ENTER an...

Page 7: ...ce to return to RUN mode PT 1 3 Adjustment method and procedure same as dEAdZONE 4 Push DOWN 7 times at dEAdZONE mode and PT mode is displayed 5 Push ENTER at PT mode and PT message appears on LCD 6 A...

Page 8: ...according to the field conditions the user s need Tight Shut Open TSHUT OP This allows the user to fully open valve at any value around the 20 mA current input signal Tight Shut Close TSHUT CL This a...

Page 9: ...re any problems during Series 185 and 285 positioner operation you can check the error and warning code at VIEW mode as follows Error Code This code is displayed when the Series 185 and 285 positioner...

Page 10: ...s below 500 The angle of feedback lever is too small Time elapsed for either full open or full close is less than 1 second The size of the actuator is too small Pv zero is below 100 The angle of feedb...

Reviews: