SPECIFICATIONS
Input Signal:

4 to 20 mA DC.

Input Impedance: 

460 Ω max @ 20 mA DC.

Enclosure: 

Aluminum, SS. 

Air Supply: 

35 to 116 psi (3.5 to 9 bar).

Air Connection: 

1/4˝ NPT.

Gage Connection: 

1/8˝ NPT.

Conduit Connection: 

1/2˝ NPT.

Linearity: 

±0.5% FS.

Hysteresis: 

±0.5% FS.

Sensitivity: 

±0.2% FS.

Repeatability:

±0.3% FS.

Air Consumption: 

.0004 scfm (.01 LPM) at 20 psig (1.4 bar) supply.

Flow Capacity: 

2.1 scfm (60 LPM) at 20 psig (1.4 bar) supply.

Stroke: 

185: 0.5 to 6 in (10 to 150 mm); 285: 0 to 90°. 

Enclosure Rating: 

NEMA 4X (IP66).

Temperature:

Operating: -22 to 185°F (-30 to 85°C).

Weight: 

185: 3.3 lb (1.5 kg); 285: 6.4lb (2.9 kg).

Lever:

185: .39 to 1.57 in (10 to 40 mm); 285: NAMUR.

The Series 185 and 285 Smart Positioners

control valve movements accurately

using an input signal of 4 to 20 mA from the controller. In addition, a highly efficient
microprocessing operator built into the product performs various functions such as
auto calibration, PID control, alarm and Hart

®

protocol.

Features

• LCD allows the user to directly check the positioner condition in the field.
• Endures severe vibration.
• Operates normally regardless of changes in supply pressure during operation.
• Simple to use auto calibration.
• Easily equipped on small actuators because of its small size.
• Low air consumption reduces operating cost.
• Can be used in low voltage (8.5 V), leaving no limitation in controller.
• Variable orifice is applied in case of a small actuator; the hunting is controlled

to the optimum condition during operation.

• HART

®

communication processes various information for the valve and

positioner.

• Valve system is stabilized by outputting analog feedback signal.
• The adjustment of valve characteristics (linear, quick open, equal percentage)

is available.

• Specific flow control is available with setting 16 points at users’ command.
• Tight shut-close and shut-open can be set voluntarily.
• PID parameters can easily be adjusted in the field without additional

communicator.

• The pressure of air filter regulator is sent directly to actuator using A/M

switch.

• Split ranges such as 4 to 20 mA, with 12 to 20 mA available. 
• Setting zero and span as partial section is available by hand calibration

function.

• The valve defect is easily checked because the valve can be operated

voluntarily.

• Air filter regulator can be attached to the product with only one linear nipple

without extra piping.

 

LCD SCREEN

SMART POSITIONER

3-27/32

[97.50]

3-1/64

[76.50]

4-7/64

[104.20]

SUPPLY
1/4 NPT

2-33/64

[64.00]

2-11/32

[59.60]

4-13/32

[111.90]

STAINLESS STEEL

4-31/64

[113.8]

STANDARD

CONDUIT ENTRY

1/2 NPT

8-31/64

[215.70]

DOUBLE

ACTION

SINGLE
ACTION

3-47/64

[95.00]

Series 185

Series 285

HART

® 

is a registered trademark of Hart Communication Foundation

Summary of Contents for 185 Series

Page 1: ...essure during operation Simple to use auto calibration Easily equipped on small actuators because of its small size Low air consumption reduces operating cost Can be used in low voltage 8 5 V leaving...

Page 2: ...5 Four M8 plate washers Installing Series 185 with Bracket It is necessary to make a proper bracket to attach on the actuator yoke The most important considerations in the design of the bracket are as...

Page 3: ...gulator on the actuator When the stroke is both 0 and 100 the feedback lever should not reach to the lever stopper on the backside of the Series 185 unit If the feedback lever reaches the lever stoppe...

Page 4: ...o NAMUR shaft 5 Once the fork lever position is set lock the check nuts on the bottom of the fork lever by turning clockwise Set the upper height of the fork lever to 24 to 43 6 to 11 mm lower than th...

Page 5: ...the positioner and system 2 The ground terminals are inside the terminal in the center of the terminal plate and outside terminal beside outer cable entry Use any ground terminal that is available and...

Page 6: ...by users in the field after being supplied the positioner unit whose parameters were set by the valve company 1 Push ENTER for 6 seconds in RUN mode and AUTO CAL message should appear 2 Push ENTER an...

Page 7: ...ce to return to RUN mode PT 1 3 Adjustment method and procedure same as dEAdZONE 4 Push DOWN 7 times at dEAdZONE mode and PT mode is displayed 5 Push ENTER at PT mode and PT message appears on LCD 6 A...

Page 8: ...according to the field conditions the user s need Tight Shut Open TSHUT OP This allows the user to fully open valve at any value around the 20 mA current input signal Tight Shut Close TSHUT CL This a...

Page 9: ...re any problems during Series 185 and 285 positioner operation you can check the error and warning code at VIEW mode as follows Error Code This code is displayed when the Series 185 and 285 positioner...

Page 10: ...s below 500 The angle of feedback lever is too small Time elapsed for either full open or full close is less than 1 second The size of the actuator is too small Pv zero is below 100 The angle of feedb...