17
Lockout
Keypad lockout levels
Default value =
0 No lock
0 = No lock
1 = Low level
2 = High level
Level
Resume/
Override
scheduling
Permanent
Occupied and
Unoccupied
Setpoints
Temporary
setpoints
using arrows
Humidity
Setpoints
System mode
setting
Fan mode
setting
Schedules
setting
Clock setting
Permanent
hold
Resume
sched Y/N
Temperat
set Y/N
Up key (
▲
)
Down key (
▼
)
Humidity
set Y/N
Sys mode
set Y/N
Fan mode
set Y/N
Schedule
set Y/N
Clock
set Y/N
Schedule
hold Y/N
0
Yes access
Yes access
Yes access
Yes access
Yes access
Yes access
Yes access
Yes access
Yes access
1
Yes access
No access
Yes access
No Access
No access
No access
No access
Yes access No
access
2
No access
No access
No access
No Access
No access
No access
No access
Yes access
No access
Pwr del
Power-up delay
Default value =
10 seconds
On initial power up of the thermostat (each time 24 Vac
power supply is removed & re-applied) there is a delay
before any operation is authorized (fan, cooling or
heating). This can be used to sequence start up multiple
units / thermostat in one location.
10 to 120 seconds
Frost pr
Frost protection enabled
Default value =
Off
On
heat pump
models the system mode
will be forced to EMERGENCY mode if
frost protection is activated
Off:
no room frost protection
On:
room
frost protection enabled in all system mode at:
42 °F ( 5.6 °C )
Frost protection is enabled even in system
Off
mode
Off or On
Heat max
Maximum heating setpoint limit
Default value =
90 °F ( 32 °C )
Maximum occupied & unoccupied heating setpoint
adjustment. Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
Cool min
Minimum cooling setpoint limit
Default value =
54 °F ( 12 °C )
Minimum occupied & unoccupied cooling setpoint
adjustment. Cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
Pband
Proportional Band setting
Default value =
2.0 °F ( 0.6 °C )
Adjust the proportional band used by the thermostat PI
control loop.
Warning.
Please note that the default value of 2.0 °F ( 0.6
°C ) gives satisfactory operation in most normal
installation cases. The use of a superior proportional band
different than the factory one is normally warranted in
applications where the thermostat location is problematic
and leads to unwanted cycling of the unit. A typical
example is a wall mounted unit where the thermostat is
installed between the return and supply air feeds and is
directly influenced by the supply air stream of the unit.
Value
F scale
Pband
C scale
Pband
2
2 F
0.6 C
3
3 F
1.2 C
4
4 F
1.7 C
5
5 F
2.2 C
6
6 F
2.8 C
7
7 F
3.3 C
8
8 F
3.9 C
Anticycle
Minimum on/off operation time for stages
Default value =
2 minutes
Anti-short cycling can be set to 0 minutes
for equipment that posses their own anti
cycling timer. Do not use that value
unless the equipment is equipped with
such internal timer. Failure to do so can
damage the equipment.
Minimum On/Off operation time of cooling & heating
stages.
IMPORTANT, anti-short cycling can be set to 0 minutes
for equipment that posses their own anti cycling timer. Do
not use this value unless the equipment is equipped with
such internal timer. Failure to do so can damage the
equipment.
0, 1, 2, 3, 4 & 5 minutes