16
Channel
Channel selection
Default value =
10
Range is:
10 to 26
Conditional parameter to Wireless models
(VT76xxX5x28W)
This parameter will only appear when a wireless network
adapter is present. If the thermostat is installed as a stand-
alone unit or with a BACnet or Echelon adapter, this parameter
will not be used or displayed
This parameter (Channel) is used to link specific thermostats to
a specific Vykon JACE with wireless network adapter. For
every thermostat reporting to a JACE (maximum of 30 wireless
thermostats ), be sure you set the
SAME
channel value both at
the JACE and the thermostat(s).
Vykon recommends using only the 2 last channels ( 25-
2575MHz and 26-2580MHz )
The default value of 10 is
NOT
a valid channel. The valid range
of available channel is from 11 to 26
%RH disp
Local RH Display
Default value =
Off
Enables the display of humidity below the room
temperature on the display
On
= Display %RH
Off
= No display of %RH
DI
Digital input no.1 configuration
Open contact input = function not
energized
Closed contact input = function
energized
Default value =
None
None
, No function will be associated with the input
Rem NSB
, remote NSB timer clock input. Will disable
the internal scheduling of the thermostat. The scheduling
will now be set as per the digital input. The time is still
displayed as information, but the menu part related to
scheduling is disabled and no longer accessible.
Open contact = occupied setpoints
Closed contacts = unoccupied setpoints
RemOVR
Temporary override remote contact. Disables
all override menu function of the thermostat. The
override function is now controlled by a manual remote
momentarily closed contact. When configured in this
mode, the input operates in a toggle mode. With this
function enabled it is now possible to toggle between
unoccupied & occupied setpoints for the amount of time
set by parameter (TOccTime) temporary occupancy
time. When Override is enabled, an Override status
message will be displayed
Filter,
a back-lit flashing
Filter
alarm will be displayed
on the thermostat LCD screen when the input is
energized
Service,
a back-lit flashing
Service
alarm will be
displayed on the thermostat LCD screen when the input
is energized
Fan lock,
a back-lit flashing
Fan lock
alarm will be
displayed on the thermostat LCD screen when the input
is not energized. Used in conjunction with a local airflow
sensor connected to the input. Locks out the thermostat
heating and cooling action if no airflow is detected 10
seconds after the fan ( G terminal ) is energized.
Open contact = no airflow
Closed contacts = airflow present
MenuScro
Menu scroll
Default value =
On =
Scroll active
Removes the scrolling display and only present the room
temperature/humidity to the user. With this option
enabled, no status is given of mode, schedule and
outdoor temperature.
On = Scroll active
Off = Scroll not active