Theory of operation 

 

 

 

The VT76x7 uses a Viconics proprietary adaptive logic 
algorithm to control the space temperature. This 
algorithm controls the heating / air conditioning system 
to minimize overshoots while still providing comfort. It 
provides exceptional accuracy due to its unique PI 
time proportioning control algorithm, which virtually 
eliminates temperature offset associated with 
traditional, differential-based on/off thermostats. 
 
 
 
 
 
 
 
 
 
 

 

Fig.2 - On/Off mechanical control vs PI electronic control. 

 
Features overview 

 

 

 

  7 day programmable models, 2 or 4 events 

 

Gas/oil or electric system compatibility for all type 
of applications 

 

Internal RH sensor and remote RH input with 
humidification and dehumidification sequence of 
operation embedded 

 

Remote outdoor sensing capability for added 
flexibility 
-  System mode lock out  
-  Humidity setpoint reset 

 

High limit input to prevent over-humidification 

 

Lockable keypads for tamper proofing. No need for 
thermostat guards 

 

Automatic frost protection to prevents costly freeze 
damage 

 

Anti short cycle and minimum on/off run time 
protection. Reduces wear and maximizes life span 
of mechanical equipment. 

 

  Programmable digital input for added flexibility. The 

input can be programmed as the following: 

None: 

No function will be associated with the 

input  

Service: 

a backlit flashing 

Service 

alarm will be 

displayed on the thermostat LCD screen when 
the input is energized. It can be tied in to the AC 
unit control card, which provides an alarm in 
case of malfunction.

 

Filter: 

a backlit flashing 

Filter 

alarm will be 

displayed on the thermostat LCD screen when the 
input is energized. It can be tied to a differential 
pressure switch that monitor filters

 

Rem NSB:

 remote NSB timer clock input. Will 

disable the internal scheduling of the thermostat. 
The scheduling will now be set as per the digital 
input. The menu part related to scheduling is 
disabled and no longer accessible. It provides low 
cost setback operation via occupancy sensor or 
from a dry contact

 

RemOVR:

 temporary occupancy contact.  Disables 

all override menu function of the thermostat. . The 
override function is now controlled by a manual 
remote momentarily closed contact. When 
configured in this mode, the input operates in a 
toggle mode. 
With this function enabled it is now possible to 
toggle between unoccupied & occupied setpoints 
for the amount of time set by parameter 
(TOccTime) temporary occupancy time. 

Fan lock: 

used in conjunction with a local airflow 

sensor connected to the input. Locks out the 
thermostat heating and cooling action and displays 
a local alarm if no air flow is detected 10 seconds 
after the fan ( G terminal ) is energized. 
 

 

Programmable smart fan operation saves 
energy during night mode  

 

Non volatile EEPROM memory prevents loss of 
parameters during power shortage 

 

Built in default profile set-up for easier start up 
and commissioning 

 

Configurable SPST output relay on 
programmable models for lighting, exhaust fan 
or fresh air control 

 

6 hour typical reserve time for clock in case of 
power loss 

 

0 to 10 Vdc humidification output 
-  Built in proportional humidity controller 
-  Proportional humidity high limit when used 

with the analog input for supply humidity 

-  Automatic humidity setpoint reset when 

outside air temperature value is used. 

 

Summary of Contents for VT7607B5x28(X)

Page 1: ...dy VT6x7 Series LonWorks Integration Guide VYKONStat PIR Application Guide VYKONStat PIR Cover Assembly Installation Guide VYKONStat Wireless Controller Application Guide Models Available Application...

Page 2: ...2...

Page 3: ...er alarm will be displayed on the thermostat LCD screen when the input is energized It can be tied to a differential pressure switch that monitor filters Rem NSB remote NSB timer clock input Will disa...

Page 4: ...push on it until the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correc...

Page 5: ...internal wiring Jumper J1 T1 24 Vac Cool Stage 2 Y2 Y1 Jumper J1 See note 1 previous page Fan RC G C Heat Stage 1 W1 RH W2 Auxiliary Output Field contact Com 24V Remote Outdoor Sensor Digital Input 0...

Page 6: ...hermostat Remote humidity sensor accessories Model no Description VH2020W1028 Wall mounted humidity sensor VH2020D1028 Duct mounted humidity sensor VH2020W1028 remote wall mounted room humidity sensor...

Page 7: ...e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o...

Page 8: ...122 F indicates a shorted sensor Associated functions such as mode lockouts are automatically disabled A minimum range status 40 C 40 F is not displayed and indicates a opened sensor or a sensor not...

Page 9: ...increase temperature setpoint and to adjust the desired values when programming and configuring the thermostat When left unattended for 45 seconds the display will resume automatic status display scr...

Page 10: ...will be prompted with the present mode Heating or Cooling of the thermostat and its setpoint The Up arrow key will increment the setpoint by 0 5 degree F or C The Down arrow key will decrement the set...

Page 11: ...ehumidification output is then activated There is NO active temperature lockout protection in this mode If the dehumidification process causes the room temperature to rise or fall the thermostat will...

Page 12: ...00 00 AM Use To set value Unoccup 00 00 AM Use To set value Sets Event 2 Unoccupied time Will activate unoccupied setpoints Use to set value Yes key to confirm Typical examples of a 2 event office sc...

Page 13: ...e Will activate unoccupied setpoints Use to set value Yes key to confirm Ex 1 Four event retail establishment schedule Event Period 1 Event 1 Period 1 Event 2 Period 2 Event 3 Period 2 Event 4 Setpoin...

Page 14: ...3 hours Use to set value Yes key to confirm Schedule resume Resume regular scheduling cancels the permanent hold and re enables the regular programming as set per internal scheduling or as per remote...

Page 15: ...orking address Default value 254 Range is 0 to 254 Conditional parameter to BACnet MS TP models VT76xxX5x28B Conditional parameter to Wireless models VT76xxX5x28W This parameter will only appear when...

Page 16: ...ut the menu part related to scheduling is disabled and no longer accessible Open contact occupied setpoints Closed contacts unoccupied setpoints RemOVR Temporary override remote contact Disables all o...

Page 17: ...32 C Maximum occupied unoccupied heating setpoint adjustment Heating setpoint range is 40 to 90 F 4 5 to 32 0 C Cool min Minimum cooling setpoint limit Default value 54 F 12 C Minimum occupied unoccup...

Page 18: ...or On or Auto fan mode When selecting Off the fan terminal G when heating stages terminals W1 W2 are solicited will not be energized The fan in this case will be controlled by the equipment fan limit...

Page 19: ...toggles from occupied to unoccupied after the last movement has been detected by the PIR Range is 0 5 to 24 0 hours in 0 5 hour increments 2 4event Number of events configuration Default value 2 even...

Page 20: ...network value is transmitted to the thermostat See RH LT RE Sp From 20 F up to 55 F 6 5 C to 13 C HL Sp RH High limit setpoint Default value 85 RH High humidity limit in the supply Only valid if a 0 1...

Page 21: ...et that can be added subtracted to actual displayed humidity by 15 0 RH This calibration applies to the internal humidity sensor if no remote humidity sensor is connected This calibration applies to t...

Page 22: ...e 8 RE Sp was set to 20 therefore the humidity setpoint dropped from 45 to 20 If you don t want to use this feature set the RE Sp parameter to 90 RH High limit humidity sensor The VT76x7 series includ...

Page 23: ...etpoint mode for the new setpoint to be kept and memory and used all the time 2 Go to the Set temperature menu 3 The last prompt is setpoint type Set it to Permanent setpoint Wrong mode selected Selec...

Page 24: ...erify wiring Digital display shows missing digits or erratic segments Defective display Replace thermostat RH sensor is out of range Verify the remote RH sensor or the internal RH sensor System Mode i...

Page 25: ...0 Vdc into 2K resistance min Humidification analog output accuracy 3 typical Wire gauge 18 gauge maximum 22 gauge recommended Dimensions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg...