2.1.1.7 The height of the sweating room shall be at least 1.9 m.
2.1.1.8 The vertical distance between the EH top and the premise ceiling shall be at least 1.0 m.
2.1.1.9 The floor area, where the EH will be installed, as well as wall sections near the EH shall be
protected with a non-combustible, heat-insulating material. A heat-insulating sheet for the floor
protection is not included into delivery and shall be purchased additionally.
2.1.1.10 The ceiling above the EH shall be protected with a heat-insulating shield made of a non-
combustible material. The distance between the ceiling and the shield shall be at least 50.0 mm.
2.1.1.11 The room, where the EH shall be installed, shall be ventilated. Supply and exhaust openings
shall be located correspondingly at the floor and ceiling, on the room diagonal. To prevent the
wrong operation of the temperature control system in the stove, no air supply under the EH is
permitted!
2.1.1.12 Only one EH may be used in a room.
2.1.1.13 The cable used for the EH connection shall be wrapped with the heat-resistant insulation
SiHF/GL-P. Russian equivalents are: PVKV, RKGM, PNBS, etc. Cable core sections shall be at least equal
to the section specified in 1.2 hereof. For costs saving, the EH may be connected using a non-heat-
resistant insulation till a pull (terminal) box in a low-temperature, water-protected area. Ends of the
cable cores, which are connected to the EH and CP shall be equipped with special lugs.
2.1.1.14 The Electric heater must not be operated without protective automatic circuit breaker. For
the Electric heater connection, an automatic circuit breaker shall be provided, with a rated current,
which corresponds to the Electric heater power consumption. The automatic circuit breaker shall