2. APPLICATION
2.1 Preparation to use.
Attention! Walls and ceiling of the sweating room shall be well heat-insulated. We recommend to
face the sweating or sauna room with wood. Remember that the use of decorative heat-absorbing
materials (stone, bricks, tiles, etc.) for the heat accumulation requires additional time and electric
power for their heating.
2.1.1 Safety precautions
2.1.1.1 To ensure the strict compliance with fire and electrical safety rules, the Electric heater shall be
connected by electricians, who have certificates allowing their work with electric installations up to
1000 V, and at least III certification level for electrical safety.
2.1.1.2 Electrical wiring shall be conducted according to the Electrical Installation Code (PUE) and
Safety Rules.
2.1.1.3 The Electric heater shall be commissioned against a corresponding certificate.
2.1.1.4 The Electric heater must not be installed in premises, which do not correspond to fire safety
rules established by the RF Government Regulation dd. April 25, 2012 no. 90, SP 60.13330.2016,
SP 7.13130.2013.
2.1.1.5 The Electric heater power shall correspond to the sweating room volume.
2.1.1.6 The distance from the EH enclosure to the wall facing shall be at least 150 mm for the Electric
heater 4-6 kW, at least 200 mm for the Electric heater 12, 16 kW, at least 250 mm for the Electric heater
18-24 Kw.