CS2 R30252.xx
from 75A to 200A
User’s manual
27
Supply the electronic board
The thyristor unit, to work, requires a voltage supply for the electronic boards of 24Vdc 1A on Terminal M1 (5, 6)
and the Synchronization signal between terminals 1 and 3.
The voltage used on Terminal 1 and 3 must be the same of load voltage (L1-L2/N).
Warning:
Before connecting or disconnecting the unit check that power and control cables
are isolated from voltage sources.
Terminal M1
Description
1
Voltage for synchronization signal
2
Not used
3
Voltage for synchronization signal
4
Not used
5
24Vdc - Auxiliary supply and Fan supply
6
24Vdc + Auxiliary supply and Fan supply
11