CS2 R30252.xx
from 75A to 200A
User’s manual
13
Technical Specifications
3 1 General features
Cover and Socket material:
PolymericV2
Utilization Category:
AC-51 AC-55b
IP Code:
20
Method of Connecting:
Load in Delta, Load in Star
Auxiliary voltage:
24Vdc (1A)
Relay output for Heater Break Alarm
0.5A a 125VAC
(only with HB option)
3 2 Input features
Digital Input:
4 ÷ 30Vdc 5mA Max (ON ≥ 4Vdc OFF < 1Vdc) 5Hz max
Volt Analogic input:
0 ÷ 10Vdc impedance 15 K ohm
Current Analogic input:
4 ÷ 20mA impedance 100 ohm
POT:
10 K ohm min.
Logic input SSR (Fast Enable):
4 ÷ 30Vdc 5mA Max (ON >
4Vdc OFF <1Vdc)
3HZ Max duty cycle min. 100 ms)
3 3 Output features (power device)
Current
Output
Voltage
range (Ue)
Repetitive
peak reverse
voltage
(Uimp)
Latching
current
Max peak
one cycle
Leakage
current
FUSE I2T value
Suggested A2s
(at 660V)
Frequency
range
Power loss
Thyristor
+ Fuse
Isolation
Voltage
(Ui)
(A)
(V)
(480V) (600V)
(mAeff)
(10msec.)
(A)
(mAeff)
tp=10msec
(Hz)
I=Inom (W)
Vac
75A
24÷600
1200
1600
450
2000
15
19100
47÷70
255
2500
125A
24÷600
1200
1600
450
2000
15
19100
47÷70
255
2500
150A
24÷600
1200
1600
300
5250
15
128000
47÷70
268
2500
200A
24÷600
1200
1600
300
5250
15
128000
47÷70
380
2500
3 4 Environmental installation conditions
Ambient temperature 0-40°C (32-104°F) at nominal current.
Over 40°C -104°F use the derating curve.
Storage temperature -25°C to 70°C -13°F to 158°F
Installation place
Don’t install at direct sun light, where there are conductive
dust, corrosive gas, vibration or water and also
in salty environmental.
Altitude
Up to 1000 meter over sea level. For higher altitude
reduce the nominal current of 2% for each 100m over 1000m
Humidity
From 5 to 95% without condense and ice
Pollution Level
Up to 2nd Level ref. IEC 60947-1 6.1.3.2