— 7 —
C24EA SERIES ELECTRIC COUNTER CONVECTION STEAMERS
ELECTRICAL CONNECTION
Electrical and
grounding connections must comply
with the applicable portions of the
National Electrical Code and/or other
local electrical codes.
The wiring diagram is located on the right side
panel as you face the steamer. This steamer is
hard wired.
Total
KW
Volts
Hz
Ph
KW Per Phase
Rated Amps
Single
Phase
Circuit
Size
Amps
Fuse
Size or
Circuit
Breaker
Size*
(Amps)
90°C
Copper
Min.
Wire
Size
3-Phase Amps Per Line
L1-L2
L2-L3
L3-L1
L1
L2
L3
8.5
208
50/60
1
40.87
60
60
8
8.5
240
50/60
1
35.42
50
50
8
8.5
208
50/60
3
4.25
2.12
2.12
26.54
26.54
17.70
35
35
10
8.5
240
50/60
3
2.83
2.83
2.83
20.50
20.50
20.50
30
25
10
8.5
480
50/60
3
2.83
2.83
2.83
10.30
10.30
10.30
15
15
16
9.25
208
50/60
1
43.57
60
60
6
9.25
240
50/60
1
38.54
50
50
8
9.25
208
50/60
3
4.25
2.69
2.12
26.54
28.88
20.04
35
35
10
9.25
240
50/60
3
2.83
3.58
2.83
20.45
23.15
23.15
30
30
10
9.25
480
50/60
3
2.83
3.58
2.83
10.21
11.57
11.57
15
15
16
15
208
50/60
1
72.12
90
90
4
15
240
50/60
1
62.50
75
75
6
15
208
50/60
3
7.50
3.75
3.75
46.84
46.84
31.23
60
60
6
15
240
50/60
3
5.00
5.00
5.00
36.08
36.08
36.08
50
50
8
15
480
50/60
3
5.00
5.00
5.00
18.04
18.04
18.04
25
25
14
15.75
208
50/60
1
74.82
90
90
4
15.75
240
50/60
1
65.63
80
80
4
15.75
208
50/60
3
7.50
4.31
3.75
46.84
49.18
33.57
60
60
6
15.75
240
50/60
3
5.00
5.75
5.00
36.08
38.79
38.79
50
50
8
15.75
480
50/60
3
5.00
5.75
5.00
18.04
19.40
19.40
25
25
14
2002 National Electric Code
*Dual Element Time-Delay Fuse or Inverse Time Circuit Breaker
Circuit Size (minimum) & Fuse/Circuit Breaker Size (maximum) compiled in accordance with the
National Electrical Code (ANSI/NFPA 70), 2002 Edition.