VTS2000 Series frequency inverter
- 64 -
when entering
sleep and the
set pressure
F3.15
Pipe Burst
detection
delay time
Set delay time of the pipe burst detection
0.0
~
130.0s
30.0S
○
F3.16
High pressure
detection
threshold
When the feedback pressure is greater than or equal
to this set value, the burst pipe fault "EPA0" will be
reported after F3.15 burst pipe delay. When the
feedback pressure is less than this set value, the
burst pipe fault "EPA0" will be automatically reset;
the threshold is the percentage of constant pressure.
0.0
~
200.0
%
150.0%
○
F3.17
Low pressure
detection
threshold
When the feedback pressure is less than this set
value, the burst pipe fault "EPA0" will be reported
after F3.15 burst pipe delay. When the feedback
pressure is greater than or equal to this set value, the
burst pipe fault "EPA0" will be automatically reset;
0.0
~
200.0
%
50.0%
○
Summary of Contents for VTS2000 Series
Page 1: ...VTS2000 Series Frequency Inverter User Manual Controlling and protecting your motor...
Page 14: ...VTS2000 Series frequency inverter 12 2 Installation and wiring 1 Dimensions...
Page 16: ...VTS2000 Series frequency inverter 14 2 Basic wiring diagram...
Page 21: ...VTS2000 Series frequency inverter 19 3 Operation panel introduction...
Page 96: ......
Page 111: ...VTS2000 Series frequency inverter 15 2 Instalacja i okablowanie 1 Wymiary...
Page 113: ...VTS2000 Series frequency inverter 17 2 Podstawowy schemat po cze...
Page 114: ...VTS2000 Series frequency inverter 18 3 Korespondencja skoczk w...
Page 121: ...VTS2000 Series frequency inverter 25 3Wprowadzenie do panelu operacyjnego...
Page 123: ...VTS2000 Series frequency inverter 27 ci stotliwo ci...
Page 192: ......