VTS2000 Series frequency inverter
- 63 -
threshold
coefficient
value, and when the frequency output by the inverter
reaches the lower limit frequency, the inverter enters
the sleep state (ie, running at zero speed) after the
delay waiting time defined by F3.12; The value is
the percentage of PID setting.
F3.11
Wake up
threshold
coefficient
If the actual feedback value is less than the given
value, the inverter will leave the sleep state and start
working after the delay waiting time defined by
F3.13; this value is the percentage of the PID set
value.
0.0
~
150.0%
90.0
%
○
F3.12
Sleep delay
time
Set sleep delay time
0.0
~
999.9s
100.0s
○
F3.13
Wake up
delay time
Set wake up delay time
0.0
~
999.9s
1.0s
○
F3.14
The deviation
between the
feedback
This function parameter is only valid for disturbance
sleep mode
0.0
~
10.0
%
0.5%
○
Summary of Contents for VTS2000 Series
Page 1: ...VTS2000 Series Frequency Inverter User Manual Controlling and protecting your motor...
Page 14: ...VTS2000 Series frequency inverter 12 2 Installation and wiring 1 Dimensions...
Page 16: ...VTS2000 Series frequency inverter 14 2 Basic wiring diagram...
Page 21: ...VTS2000 Series frequency inverter 19 3 Operation panel introduction...
Page 96: ......
Page 111: ...VTS2000 Series frequency inverter 15 2 Instalacja i okablowanie 1 Wymiary...
Page 113: ...VTS2000 Series frequency inverter 17 2 Podstawowy schemat po cze...
Page 114: ...VTS2000 Series frequency inverter 18 3 Korespondencja skoczk w...
Page 121: ...VTS2000 Series frequency inverter 25 3Wprowadzenie do panelu operacyjnego...
Page 123: ...VTS2000 Series frequency inverter 27 ci stotliwo ci...
Page 192: ......