VTS2000 Series frequency inverter
- 62 -
not set.
F3.06
Sampling
period T
The larger the sampling period, the slower the
response, but the better the suppression effect of the
interference signal, it is not necessary to set it under
normal circumstances.
0.1
~
10.0s
0.0s
○
F3.07
Deviation
limit
The deviation limit is the ratio of the absolute value
of the deviation between system feedback amount
and the given amount to the given amount. When the
feedback amount is within the deviation limit range,
the PID adjustment does not work.
0.0
~
20.0
%
0.0
%
○
F3.08
Closed loop
preset
frequency
Frequency and running time of inverter before PID
operation
0.0
~
Upper limit
frequency
0.0Hz
○
F3.09
Preset
frequency
retain time
0.0
~
999.9s
0.0s
×
F3.10
Sleep
If the actual feedback value is greater than the given
0.0
~
150.0%
100.0
%
○
Summary of Contents for VTS2000 Series
Page 1: ...VTS2000 Series Frequency Inverter User Manual Controlling and protecting your motor...
Page 14: ...VTS2000 Series frequency inverter 12 2 Installation and wiring 1 Dimensions...
Page 16: ...VTS2000 Series frequency inverter 14 2 Basic wiring diagram...
Page 21: ...VTS2000 Series frequency inverter 19 3 Operation panel introduction...
Page 96: ......
Page 111: ...VTS2000 Series frequency inverter 15 2 Instalacja i okablowanie 1 Wymiary...
Page 113: ...VTS2000 Series frequency inverter 17 2 Podstawowy schemat po cze...
Page 114: ...VTS2000 Series frequency inverter 18 3 Korespondencja skoczk w...
Page 121: ...VTS2000 Series frequency inverter 25 3Wprowadzenie do panelu operacyjnego...
Page 123: ...VTS2000 Series frequency inverter 27 ci stotliwo ci...
Page 192: ......