SPECIFICATIONS

POWER SUPPLY

24 VAC system

18 – 30 VAC, 50/60 Hz

TEMPERATURE :

Temperature accuracy

±

 1.8

 °

F

Storage temperature

32 – 158 

°

Ambient temperature

50 – 122 

°

F

Setting temperature range

64 – 85 

°

F

Deadband (Auto changeover model)

±

 1

 °

F of Setpoint

HEAT and COOL RELAY : ( P1, P2)

Rating (resistive load)

 

 Maximum switching capacity

3 A 277 VAC

 

 Delay Time

1 minute or 3 minute (default)

FAN RELAY: (P3, P4, P5)

Rating (resistive load)

  

Maximum switching capacity

2 A 277 VAC

3 A 125 VAC

INSTALLATION

Read   these   instructions   thoroughly  before   installing   product.   Failure   to   follow   these   instructions   could 
damage the product or cause a hazardous condition. Check the voltage and current ratings on the product to 
ensure that it is suitable for your application. Installer must be a trained, experienced service technician. 
Check product for proper operation after installation.

CAUTION

Damage to heating and cooling system may occur. Disconnect power from the equipment at the main 

breaker/fuse block while installing the thermostat.

Mounting Location

Mount  the  thermostat  approximately  5  ft. (1.5m)   above  the  floor  in a  location  that  is free  from  direct 
sunlight, heat from appliances, hot or cold air from ducts, concealed pipes and chimneys, and drafts or dead 
spots behind doors or in corners.  Do not mount on exterior wall, if possible.  Failure to locate thermostat 
mounting as indicated will result in poor temperature control.

Note

 : Level thermostat mounting is for appearance only and is not required for proper thermostat operation.

2