background image

Vtronix

Auto mode

The speed will be adjusted according to the difference between the room and the setpoint temperature.

If the difference is 4

°

F or more, the fan will run at high speed.

If the difference is 3

°

F, the fan will run at medium speed.

If the difference is 2

°

F, or lower, the fan will run at low speed.

Note : Fan speed defaults to Automatic after 1 hour if it is changed by the user to a particular speed.

C

   ontinuous Fan

 

 

FAN is always on in High, Medium or Low speeds as long as the thermostat is powered.

C

   ycled Fan Standard

 

 

Fan is on when the heat or cool outputs are on (on cycle).   Automatic fan operation is active in the on cycle.  
When the heat or cool outputs are off (off cycle), the Fan output is off.  The Fan LEDs (Auto, High, Med and  
Low) are all turned off.  The Fan button is deactivated in the off cycle.  During the on cycle the fan speed can 
be manually changed.  The fan will turn off in the off cycle and revert back to the selected fan speed during  
the on cycle.

C

   ycled Fan Override

 

 

Fan is on when the heat or cool outputs are on (on cycle).  Automatic fan operation is active in the on cycle.  
When the heat or cool outputs are off (off cycle), the Fan output is off.  The Fan LEDs (Auto, High, Med and  
Low) are all turned off.  The Fan button can be activated in the off cycle.  The appropriate Fan LED (High, 
Med and Low) is turned on and the appropriate output is energized.  It stays on this speed during the on cycle 
as well as the off cycle.  This is subject to the automatic fan speed default timer.

Warning: This mode should not be selected for hydronic applications with no control valves. 
Excessive heating can result if the Fan is turned on manually.

A

   uto Fan Speed Timer

 

 

Fan speed defaults back to Automatic after 1 hour (or 3 hours based on P1 flashing setting) if it is changed to 
a particular speed.

Temperature setting 

Press TEMP  

   or   TEMP  

  button for setting the temperature in range of 64-85

°

F. But High and Low 

setting will depend on P5 and P6.
LED at  

 will show the new setting for 5 seconds.

T200 Manual changeover 

In Cool mode, setting range will be 64-85

°

F or 70-85

°

F (set in P5).

      

In Heat mode, setting range will be 64-85

°

F or 64-78

°

F (set in P6).

T201 Auto changeover 

Low setting temperature will be 64

°

F or 70

°

F (set in P5).

High setting temperature will be 85

°

F or 78

°

F (set in P6).

System status

LED at   

   turns on when there is a demand for heating or cooling. LED will flash when delay time is 

activated. Default system delay time is 3 minutes.

Sensor Error Alarm

If the thermostat temperature sensor is defective, the thermostat will turn off the equipment and start flashing 
“SE” on the display.

Auto Restart

All the setup parameters are stored in non volatile memory. When there is a power failure and return to 
normal, the thermostat will resume operation with the previous setup parameters.