5.4 Handle Switch/Run circuit 

 

Using the Handle Switch Diagnostic (DIAG #6) and the pump switches in the BYPASS position verify that the 

handle switch is detected for each pump. Turn the handles on one at a time and check that only the 
indicator for that pump is on.  Do this for all pumps attached to the VST Fuel S-810. 

5.5 Pulse Transmitters 

 

Using the Pulser Diagnostic (DIAG #5) authorize each pump and dispense a small amount of fuel to verify that the 

pulsers are counting properly. Do this for each pump one at a time. Also verify that the pulsers are 
connected to their respective pumps. 

5.6 Communications 

 
Checking out the communications circuits require the communications boards addresses and jumpers to be in the 

proper positions. Refer to the system documentation to verify that all jumpers are configured correctly (See 
Figure 17). Refer to the Operators Manual for information on communicating with the VST Fuel S-810. 

6.  WARRANTY CONDITIONS AND LIMITATIONS 

 

6.1 Warranty 

 
VST Fuel Management, Inc. warrants this product, of VST manufacture, to be free from defects in material and 

workmanship for a period of one (1) year from the date of invoice.  If VST receives written notification and 
determines that the equipment is defective within this period, VST (or its representative) will, at its option, 
repair or replace the product.  During the first ninety (90) days of the warranty period, the product will be 
repaired at no cost to the user, at the location where the product is in use.  After the first ninety (90) days of 
the warranty period, VST will repair or replace the product only if it is returned to the VST factory (at the 
Tempe facility), transportation prepaid.  The foregoing warranty will not cover reimbursement for labor, 
transportation, removal, installation or other expenses which may be incurred in connection with repair or 
replacement. 

 

This warranty shall not apply to any products which VST determines have, by the user or otherwise, been the subject 

of misuse, misapplication, neglect, alteration, damage, or improper installation, operation, maintenance, 
storage or repair. This warranty applies only when a valid Warranty Registration and Check-out Form has 
been filed with VST Fuel Management, Inc. 

 
Except as may be expressly provided in an authorized writing by VST,  VST shall not be subject to any other 

obligations or liabilities whatsoever, expressed or implied, with respect to equipment manufactured by VST 
or services rendered by VST. 

 
THE FOREGOING WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER EXPRESS AND 

IMPLIED WARRANTIES EXCEPT WARRANTIES OF TITLE, INCLUDING BUT NOT LIMITED TO 
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR 
PURPOSE. VST further disclaims any responsibility whatsoever for injury to person or damage to or loss 
of property or value caused by any product which has been subjected to misuse, negligence, or accident; or 
misapplied; or used in violation of product manuals, instructions, or warning; or modified or repaired by 
unauthorized persons; or improperly installed; or malfunctioning. 

 
 

 

 VST, 2010

 

18 

 

Summary of Contents for S-810

Page 1: ...ent contains information proprietary to VST Fuel Management Inc and shall not be disclosed duplicated or used for procurement design or manufacture without the expressed written consent of VST Fuel Ma...

Page 2: ...y precaution to prevent possible hazards which could result in serious bodily injury and property damage You are responsible for installing this product according to the instructions and warnings cont...

Page 3: ...rements 9 4 2 Wire Manufacturers 9 4 3 Dispensers Pumps 9 Table 1 Size of Dispenser Junction Box 10 b Interface wiring 11 c Dispenser wiring 11 Figure 4 Typical Wiring for 115Vac or 230 Vac VST Fuel S...

Page 4: ...on This manual provides a general description of various types of installations applicable to VST Fuel S 810 systems Installation shall be in accordance with National Electric Code NFPA 70 the Automot...

Page 5: ...Figure 1 Typical Installation of VST Fuel S 810 VST 2010 5...

Page 6: ...nsactions in memory for downloading The VST Fuel S 810 Fuel Management System has the capability of operating with a wide range of output devices which include printers modems personal computers and o...

Page 7: ...ry representative 2 2 Parts Verification Prior to starting work make sure that all of the correct parts have been received You will also need the following partial list of parts to complete the instal...

Page 8: ...d using either of two methods The first method is mounting the DET on the top of a 2 inch pipe x 55 approx height The DET is simply screwed onto the pipe and after being positioned for operation the t...

Page 9: ...Figure 2 VST Fuel S 810 Dimensions VST 2010 9...

Page 10: ...Figure 3 VST Fuel S 810 Pedestal Mounting VST 2010 10...

Page 11: ...end only AC wire size is to be minimum AWG 14 All wiring should be either color coded or numbered to facilitate connection of the wire ends CAUTION Do not use non moisture non oil proof or standard h...

Page 12: ...WARNING IN INSTALLATION AND USE OF THIS PRODUCT COMPLY WITH THE NATIONAL ELECTRICAL CODE FEDERAL STATE AND LOCAL CODES AND ANY OTHER APPLICABLE SAFETY CODES IN ADDITION TURN OFF POWER AND TAKE OTHER...

Page 13: ...rical Code to determine size of conduit required for the number of conductors b When possible install at least 25 percent spares for expansion and maintenance CAUTION NEVER RUN AC OR OTHER EQUIPMENT W...

Page 14: ...control This control may be implemented through the use of electrically operated solenoid valves 5 Pulser Wiring Each dispenser pump or hose to be controlled and monitored by the VST Fuel S 810 syste...

Page 15: ...signals CTS DCD RTS and DTR may be connected on a one for one basis if desired See Figure 13 The support of these signals is limited to providing the correct signal level for operation of the modem W...

Page 16: ...trol the correct pump When Diagnostic four is selected the display will change to the following SELECT PUMP When you press key 1 the display will change to the following 1 2 3 4 PUMPS The four pumps 1...

Page 17: ...l 810 power switch to the on position Put the VST Fuel S 810 into the keypad diagnostic mode as explained in the previous section Run the diagnostics for the display DIAG 1 and keypad entry DIAG 2 at...

Page 18: ...o the user at the location where the product is in use After the first ninety 90 days of the warranty period VST will repair or replace the product only if it is returned to the VST factory at the Tem...

Page 19: ...Fuel Management Inc in writing of any claims including claims of breach of warranty within thirty days after the facts upon which the claim is based are discovered or should have been discovered Fail...

Reviews: