background image

 

Pump motor control relay (when provided) 

 

Solenoid valve (when provided) 

 

Pump motor (when applicable). 

 
The following paragraphs in this section provide guidelines for wiring dispensers to VST Fuel S-810 systems. These 

instructions should be followed as closely as possible for proper system operation. Functional descriptions 
and drawings are provided in this section to assist installers with wiring data. 

 

B. VST FUEL S-810 INTERFACE WIRING 

 

1. Typical dispenser-to-VST Fuel S-810 field wiring diagrams are included in this section (see drawing). The VST 

Fuel S-810 connections are shown in the drawing as they appear on the back of the VST Fuel S-810 with 
the cover removed. (Installations may vary from this concept due to wiring codes and other circumstances.) 
Wiring diagrams of dispensers are used as examples only and in no way imply that the units used with the 
system must be rewired to conform with the drawings. Dispensers are shown in all drawings at the end of 
fueling with the operating handle in the off position. 

 
2. Install all interconnecting wiring using the most applicable local wiring codes and reliable installation methods. 

Wire should be installed in rigid conduit buried in a trench. When planning wire runs, the following 
specifications apply: 
a. Use Table 1 and the National Electrical Code to determine size of conduit required for the 

number 

of conductors. 

 

b. When possible, install at least 25 percent spares for expansion and maintenance. 

 
 

 

CAUTION: 

 

NEVER RUN AC OR OTHER EQUIPMENT WIRING WITH VST FUEL S-810 LOW-VOLTAGE WIRING 

UNLESS IT IS IMPOSSIBLE TO AVOID SUCH WIRE RUNS. FAILURE TO COMPLY MAY CAUSE 

MALFUNCTION OR POSSIBLE EQUIPMENT DAMAGE. 

 

 
 

c. Never run ac or other manufacturers' equipment wiring with VST Fuel S-810 wiring unless it is  

impossible to avoid such wire runs. In these cases, shielded cable with outside insulating  sheath 
must be used for low-voltage wiring. The shield must be grounded at one end only. Insulate the 
ungrounded end to prevent shorting to conduit or other wiring. 

 

Note: Shielded wire should be used only if authorized by the applicable electrical codes. 

 

 C. DISPENSER WIRING 

 
 1. One single-pole interpose relay is provided for each dispenser. Interpose relays are located inside at the rear of 

the VST Fuel S-810 housing. (See Figures 4-8 for interpose relay wiring) Relay contacts are rated at  1/3 hp 
(115 Vac @ 6 amperes,  230 Vac @ 3 amperes). 

 
 2. Terminals are provided at the rear of the VST Fuel S-810 for wiring connections to the control interpose relays, 

for wiring connections to the pulse transmitters, and for wiring connections to the handle switches.  A 
three-wire 115/230 Vac, 50/60 Hz. line input is required for ac power to the VST Fuel S-810. Screw 
terminals are located at the rear of the VST Fuel S-810 for the ac line connections. 

 

 

 VST, 2010

 

13 

 

Summary of Contents for S-810

Page 1: ...ent contains information proprietary to VST Fuel Management Inc and shall not be disclosed duplicated or used for procurement design or manufacture without the expressed written consent of VST Fuel Ma...

Page 2: ...y precaution to prevent possible hazards which could result in serious bodily injury and property damage You are responsible for installing this product according to the instructions and warnings cont...

Page 3: ...rements 9 4 2 Wire Manufacturers 9 4 3 Dispensers Pumps 9 Table 1 Size of Dispenser Junction Box 10 b Interface wiring 11 c Dispenser wiring 11 Figure 4 Typical Wiring for 115Vac or 230 Vac VST Fuel S...

Page 4: ...on This manual provides a general description of various types of installations applicable to VST Fuel S 810 systems Installation shall be in accordance with National Electric Code NFPA 70 the Automot...

Page 5: ...Figure 1 Typical Installation of VST Fuel S 810 VST 2010 5...

Page 6: ...nsactions in memory for downloading The VST Fuel S 810 Fuel Management System has the capability of operating with a wide range of output devices which include printers modems personal computers and o...

Page 7: ...ry representative 2 2 Parts Verification Prior to starting work make sure that all of the correct parts have been received You will also need the following partial list of parts to complete the instal...

Page 8: ...d using either of two methods The first method is mounting the DET on the top of a 2 inch pipe x 55 approx height The DET is simply screwed onto the pipe and after being positioned for operation the t...

Page 9: ...Figure 2 VST Fuel S 810 Dimensions VST 2010 9...

Page 10: ...Figure 3 VST Fuel S 810 Pedestal Mounting VST 2010 10...

Page 11: ...end only AC wire size is to be minimum AWG 14 All wiring should be either color coded or numbered to facilitate connection of the wire ends CAUTION Do not use non moisture non oil proof or standard h...

Page 12: ...WARNING IN INSTALLATION AND USE OF THIS PRODUCT COMPLY WITH THE NATIONAL ELECTRICAL CODE FEDERAL STATE AND LOCAL CODES AND ANY OTHER APPLICABLE SAFETY CODES IN ADDITION TURN OFF POWER AND TAKE OTHER...

Page 13: ...rical Code to determine size of conduit required for the number of conductors b When possible install at least 25 percent spares for expansion and maintenance CAUTION NEVER RUN AC OR OTHER EQUIPMENT W...

Page 14: ...control This control may be implemented through the use of electrically operated solenoid valves 5 Pulser Wiring Each dispenser pump or hose to be controlled and monitored by the VST Fuel S 810 syste...

Page 15: ...signals CTS DCD RTS and DTR may be connected on a one for one basis if desired See Figure 13 The support of these signals is limited to providing the correct signal level for operation of the modem W...

Page 16: ...trol the correct pump When Diagnostic four is selected the display will change to the following SELECT PUMP When you press key 1 the display will change to the following 1 2 3 4 PUMPS The four pumps 1...

Page 17: ...l 810 power switch to the on position Put the VST Fuel S 810 into the keypad diagnostic mode as explained in the previous section Run the diagnostics for the display DIAG 1 and keypad entry DIAG 2 at...

Page 18: ...o the user at the location where the product is in use After the first ninety 90 days of the warranty period VST will repair or replace the product only if it is returned to the VST factory at the Tem...

Page 19: ...Fuel Management Inc in writing of any claims including claims of breach of warranty within thirty days after the facts upon which the claim is based are discovered or should have been discovered Fail...

Reviews: