Register map
The actual measurement data is placed in holding registers. To read out data, you will need to use
the corresponding holding register. All data is stored in 2 16-bit registers with below register number
as start address. Read out the data with this start address and length 2.
Decimal
HEX
Description
Type
Read / Write
16
0x10
Flow in m
n
/sec
32-bit integer (x10)
Read
17
0x11
Flow in m
3
n
/hr
32-bit integer (x10)
Read
18
0x12
Flow in l
n
/min
32-bit integer (x10)
Read
19
0x13
Flow in SCFM
32-bit integer (x10)
Read
20
0x14
Flow in m
3
n
/min
32-bit integer (x10)
Read
21
0x15
Flow in sfps
32-bit integer (x10)
Read
32
0x20
Pressure in bar
32-bit integer (x10)
Read
33
0x21
Pressure in psi
32-bit integer (x10)
Read
64
0x40
Temperature in °C
32-bit integer (x10)
Read
65
0x41
Temperature in °F
32-bit integer (x10)
Read
128
0x80
Totalizer in m
3
n
32-bit integer (x10)
Read / Write*
* Writing to the totalizer will reset the totalizer to zero.
Decimal
HEX
Description
Type
Read / Write
8
0x08
Diameter
32-bit Floating point
Read / Write
9
0x09
4 .. 20 mA Max
32-bit Floating point
Read / Write
10
0x0A
4 .. 20 mA Min
32-bit Floating point
Read / Write
11
0x0B
4 .. 20 mA Unit
32-bit Floating point
Read / Write
24
0x18
Flow in m
n
/sec
32-bit Floating point
Read
25
0x19
Flow in m
3
n
/hr
32-bit Floating point
Read
26
0x1A
Flow in l
n
/min
32-bit Floating point
Read
27
0x1B
Flow in SCFM
32-bit Floating point
Read
28
0x1C
Flow in m
3
n
/min
32-bit Floating point
Read
29
0x1D
Flow in sfps
32-bit Floating point
Read
40
0x28
Pressure in bar
32-bit Floating point
Read
41
0x29
Pressure in psi
32-bit Floating point
Read
72
0x48
Temperature in °C
32-bit Floating point
Read
73
0x49
Temperature in °F
32-bit Floating point
Read
136
0x88
Totalizer in m
3
n
32-bit Floating point
Read / Write*