17
Option 1 – On/Off (fig.9)
The user can
--switch operation between “Winter” and “Summer”,
--switch the appliance on or off
--switch the operating mode between “Manual” and “Auto”
--change the speed of the fans (if in “Manual” mode),
selecting V1, V2 or V3
Option 2 – Setpoint (fig.10, 10b)
The user can,
on the first screen:
--set the temperature threshold at which the By-pass is activated, during “Winter” and “Summer” operation;
--set the CO2 threshold above which the appliance must adjust the operating speed in order to bring the carbon dioxide
level back below the threshold;
--set the humidity threshold above which the appliance must adjust the operating speed in order to bring the moisture
level back below the threshold;
on the second screen:
--switch the activation of the by-pass between “Auto” and “Manual” (manual force);
--enable/disable automatic response of the system in the event of the humidity threshold being exceeded.
Option 3 – Clock/Scheduler (fig.11a, 11b, 11c, 11d, 11e )
ENGLISH
99
ENTER
EXIT
T1
T2
T3
T4
T5
T6
T7
T8
Mode Winter
Monday 11:42
02/01/2012
Modo: Winter
Stato: On
Manual V1
[ 1 - On/Off ]
AUTO
V1
V2
V3
10a
10a
ENTER
EXIT
T1
T2
T3
T4
T5
T6
T7
T8
Mode Winter
Monday 11:42
12/11/2012
Set Temp.: Amb: Winter
21.0 °C
[ 2 - Setpoint ]
Set Temp.: Amb: Summer
26.0 °C
Set Humidity: 65.0 %
+
Set CO2:1200 ppm
10b
10b
ENTER
EXIT
T1
T2
T3
T4
T5
T6
T7
T8
Mode Winter
Monday 11:42
02/01/2012
Bypass
Auto
[ 2 - Setpoint ]
Enable RH
Enabled
Reset
Confirm
+
11a
11a
ENTER
EXIT
T1
T2
T3
T4
T5
T6
T7
T8
Mode Winter
Monday 11:42
12/11/2012
Clock setting
11 : 42
[ 3 - Clock/Scheduler
]
Date setting
12 / 11 / 2012
+
11b
11b
ENTER
EXIT
T1
T2
T3
T4
T5
T6
T7
T8
Mode Winter
Monday 11:42
12/11/2012
Enable Time Bands: Disabled
[ 3 - Clock/Scheduler
]
+
no. of Time bands: 00