Appliance combined with electronic humidity/temperature sensor
This sensor can be used to measure the temperature and relative humidity in the room. It communicates directly with the
unit's microprocessor controller and activates the various operating modes according to the readings it takes.
01-02: Sensor power supply
7-43: Humidity sensor
70-71: Temperature sensor
(fig. 22)
Unit supply voltage
The appliance is powered with a voltage of 230/1/50; a disconnector should be fitted
on the power supply wire. Please refer to the wiring diagram for sizing. (fig. 23).
Remote ON/OFF
Used for switching the unit ON/OFF from a remote location.
The connections must be potential-free.
The units are supplied as standard with jumpered terminals.
Contact closed: unit ON;
Contact open: unit OFF
(fig. 24).
39
ENGLISH
22
22
ø
ø
71
70
43
7
01
02
L1
88
13
43
DI C. PB
External
Probe
Analog
Output
Serial
RS485
Power
Supply
Relay
(8A-250V)
C NC NO
(+) (-)
(+) (-) +24V -24V
71
70
43
7
01
02
L1
88
13
43
23
23
L
N
PE
24
24
9
43
70-71: Temperature sensor