17
Table 3 Charge Mode Specifications
Utility Charging Mode
INVERTER MODEL
5KW
Charging Current (UPS)
@ Nominal Input Voltage
Default: 30A, Max.: 60A
Bulk Charging Voltage
56.4Vdc
Floating Charging Voltage
54Vdc
Charging Algorithm
3-Step
Charging Curve
Time
Battery Voltage, per cell
Charging Current, %
100%
50%
Bulk
(Constant Current)
Absorption
(Constant Voltage)
Maintenance
(Floating)
Current
Voltage
T1
T1 = 10* T0, minimum 10mins, maximum 8hrs
T0
2.43Vdc (2.35Vdc)
2.25Vdc
Table 4 General Specifications
INVERTER MODEL
5KW
Safety Certification
CE
Operating Temperature Range
0°C to 40°C
Storage temperature
-15°C~ 60°C
Dimension (D*W*H), mm
400 x 438 x 86.3
Net Weight, kg
9.1